Перевод: с французского на русский

с русского на французский

бак+трансформатора

  • 1 cuve

    1. дежа
    2. бак трансформатора

     

    бак трансформатора
    Бак, в котором размещается активная часть трансформатора или трансформаторного агрегата с жидким диэлектриком, газо- или кварценаполненного
    [ ГОСТ 16110-82]

    EN

    tank
    the vessel in which the core, yoke and windings of a transformer or reactor are contained
    [IEV number 811-26-31]

    FR

    cuve
    récipient dans lequel le circuit magnétique et les enroulements d'un transformateur ou d'une inductance sont contenus
    [IEV number 811-26-31]

    Параллельные тексты EN-RU

     

    Oil transformers
    The magnetic circuit and the windings are immersed in a liquid dielectric that provides insulation and evacuates the heat losses of the transformer.
    ...
    A holding tank is used to recover all the liquid dielectric.

    [Legrand]

    Масляные трансформаторы
    Магнитная система и обмотки трансформатора погружены в жидкий диэлектрик, служащий изоляцией и теплоносителем.
    ...
    Активная часть трансформатора находится в баке и полностью покрыта жидким диэлектриком.

    [Перевод Интент]


    Бак трансформатора
    Бак служит для установки в нем активной части трансформатора и заливки масла (некоторые баки специальных трансформаторов заполняют газом или кварцем); он состоит из обвязки 3, дна 4, рамы 2 и крышки 1 с отверстиями для крепления болтами к раме. Крышка закрывает бак и одновременно является основанием для установки расширителя, вводов, приводов переключающих устройств, баллона термосигнализатора, подъемных колец и других деталей (рис. 2). Место разъема крышки с баком уплотняют резиновой полосой, укладываемой на раму в уступ между выступающим торцом обечайки и отверстиями в раме.

    0393


    Основные части бака трансформатора

    Крышка баков трансформаторов мощностью 25 MB-А и выше приварена к обечайке. Бак имеет нижний разъем и состоит из верхней (высокой) съемной части и нижней, являющейся его основанием (днищем). Такое устройство облегчает разборку и сборку трансформаторов и не требует механизмов большой грузоподъемности, поскольку вместо активной части поднимают верхнюю часть бака.
    Для перемещения трансформаторов (при монтаже, ремонте) массой до 20 т под днищем устанавливают тележки (по две на трансформатор), при большей массе — каретки; для подъема трансформатора стропами к стенкам бака приварены крюки; для крепления охладителей и термосифонных фильтров — патрубки с фланцами; для заполнения трансформатора маслом установлены вентили.
    Баки трансформаторов III габарита и более мощных усиливают поперечными и продольными балками из стального проката (швеллер, тавр, уголок). Механическую прочность бака и непроницаемость сварных швов испытывают избыточным давлением 30—50 кПа.

    0394
    Крышка трансформатора ТМ-400/10 (вид сверху):

    1 — фланец для соединения с расширителем, 2 — рым, 3 — ввод ВН, 4 — переключатель, 5 — кран, 6 — термометр, 7 — пробивной предохранитель, 8 — ввод нейтрали НН, 9 — линейный ввод НН, 10 — крышка, 11 — место установки расширителя

    Для трансформаторов I—V габаритов применяют баки овальной формы, больших габаритов — прямоугольные, с пространственным магнитопроводом—треугольные или круглые. Их изготовляют из листовой стали; стыки листов соединяют привариванием газо- или электросваркой.

    [http://forca.ru/spravka/spravka/bak-transformatora.html]


    Тематики

    Классификация

    >>>

    Обобщающие термины

    EN

    DE

    FR

     

    дежа
    Съемная или подкатная емкость тестомесильной и взбивальной машин.
    [ ГОСТ 16318-77]

    Тематики

    • оборуд. для торговли и общест. питания

    Обобщающие термины

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > cuve

  • 2 cuve du transformateur

    Французско-русский универсальный словарь > cuve du transformateur

  • 3 bac d'expansion

    Французско-русский универсальный словарь > bac d'expansion

  • 4 bac de transformateur

    Французско-русский универсальный словарь > bac de transformateur

  • 5 cuve de transformateur

    Французско-русский универсальный словарь > cuve de transformateur

  • 6 cuve en tôle ondulée

    Французско-русский универсальный словарь > cuve en tôle ondulée

  • 7 cuve lisse

    Французско-русский универсальный словарь > cuve lisse

  • 8 cuve à radiateurs

    Французско-русский универсальный словарь > cuve à radiateurs

  • 9 réservoir d'expansion

    1. расширитель (сосуд)
    2. бак расширительный

     

    бак расширительный
    Резервуар в замкнутой системе водяного отопления для приема излишка объема воды, образующегося при ее нагревании до максимальной рабочей температуры.
    [СНиП I-2]

    бак расширительный

    Ёмкость, устанавливаемая в системе отопления для приёма излишка воды, образующегося за счёт увеличения её объёма
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    Тематики

    • отопление, горяч. водоснабж. в целом

    EN

    DE

    FR

     

    расширитель
    Сосуд, соединенный с баком трубопроводом и служащий для локализации колебаний уровня жидкого диэлектрика
    [ ГОСТ 16110-82]

    EN

    oil conservator
    expansion tank

    a vessel connected to the tank of an oil-filled transformer so as to permit free expansion and contraction of the oil to minimize the deleterious effect of contact between the oil in the main tank and the air
    [IEV number 811-26-32]

    FR

    conservateur d'huile
    réservoir d'expansion

    récipient relié à la cuve d'un transformateur dans l'huile, afin de permettre la libre dilatation de l'huile de la cuve et de réduire au minimum les effets nuisibles du contact de l'huile avec l'air extérieur
    [IEV number 811-26-32]

     

    0379
    Рис. Legrand
    Трансформатор с расширителем

    Параллельные тексты EN-RU

    Transformers with expansion tank
    To limit the previous disadvantages, an expansion tank limits the air/oil contact and absorbs the overpressure.
    However the dielectric continues to oxidise and take in water. the addition of a desiccant breather limits this phenomenon but requires regular maintenance.

    [Legrand]

    Трансформаторы с расширителем
    Расширитель ограничивает контакт масла с воздухом и компенсирует избыточное давление, что сокращает недостатки предыдущей конструкции. Тем не менее, диэлектрик поглощает влагу и непрерывно окисляется. В такой системе дополнительно применяют воздухоосушитель, благодаря чему уменьшается окисление масла, но возникает необходимость регулярного технического обслуживания.

    [Перевод Интент]

     


    Расширитель трансформатора
    Расширитель служит для локализации (компенсации) колебаний уровня масла в трансформаторе при изменении температуры. Кроме того, он уменьшает площадь соприкосновения с воздухом открытой поверхности масла и, следовательно, защищает масло от преждевременного окисления кислородом. Расширитель представляет собой металлический цилиндр, соединенный с баком трубопроводом. Существуют герметизированные трансформаторы с азотной защитой, у которых пространство между поверхностью масла и верхней стенкой расширителя заполнено азотом. Расширители устанавливают на трансформаторах напряжением 6 кВ и выше, мощностью 25 кВ-А и более. Объем расширителя выбирают таким, чтобы при всех режимах работы трансформатора от отключенного состояния до номинальной нагрузки и при колебаниях температуры окружающего воздуха от —45 до +40°С в нем было масло (обычно 8—10% объема масла, находящегося в трансформаторе).
    На рис. показан расширитель, устанавливаемый на трансформаторах III габарита. При нагревании масло из бака трансформатора по трубе, соединяющей его с патрубком 7, вытесняется в расширитель; при снижении температуры оно поступает обратно в бак. На торцовой стенке корпуса 2 расширителя установлен маслоуказатель 1 и нанесены краской три горизонтальные черты с контрольными цифрами: —45, +15 и +40°С. Это означает, что в неработающем трансформаторе уровни масла, отмеченные черточками, должны соответствовать указанным температурам окружающего воздуха. Другая торцовая стенка корпуса крепится болтами на маслоуплотняющей прокладке. Через разъем производят чистку и окраску внутренней поверхности расширителя.

    0397
    Устройство расширителя трансформаторов III габарита

    Для сбора и удаления осадков и влаги со дна расширителя предназначен отстойник 10 с отверстием, закрываемым пробкой 9 и служащим также для слива масла из расширителя. Изменение в расширителе уровня масла, а следовательно, его объема компенсируется атмосферным воздухом, поступающим в расширитель из окружающей среды через осушитель, подсоединяемый к патрубку 6. Отверстие с пробкой 5 предназначено для заполнения расширителя маслом, кольца 3 — для подъема, патрубок 4 — для соединения с предохранительной трубой. Чтобы осадки не попадали в трансформатор со дна расширителя, конец патрубка 7 выступает внутри расширителя на 50—60 мм.
    Расширитель устанавливают немного выше уровня крышки 6 трансформатора с помощью опорных пластин 12, которые приварены к кронштейнам 11, закрепляемым на крышке болтами.

    [http://forca.ru/spravka/spravka/rasshiritel-transformatora.html]

    Недопустимые, нерекомендуемые

    Тематики

    Классификация

    >>>

    Обобщающие термины

    Синонимы

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > réservoir d'expansion

  • 10 conservateur d'huile

    1. расширитель (сосуд)

     

    расширитель
    Сосуд, соединенный с баком трубопроводом и служащий для локализации колебаний уровня жидкого диэлектрика
    [ ГОСТ 16110-82]

    EN

    oil conservator
    expansion tank

    a vessel connected to the tank of an oil-filled transformer so as to permit free expansion and contraction of the oil to minimize the deleterious effect of contact between the oil in the main tank and the air
    [IEV number 811-26-32]

    FR

    conservateur d'huile
    réservoir d'expansion

    récipient relié à la cuve d'un transformateur dans l'huile, afin de permettre la libre dilatation de l'huile de la cuve et de réduire au minimum les effets nuisibles du contact de l'huile avec l'air extérieur
    [IEV number 811-26-32]

     

    0379
    Рис. Legrand
    Трансформатор с расширителем

    Параллельные тексты EN-RU

    Transformers with expansion tank
    To limit the previous disadvantages, an expansion tank limits the air/oil contact and absorbs the overpressure.
    However the dielectric continues to oxidise and take in water. the addition of a desiccant breather limits this phenomenon but requires regular maintenance.

    [Legrand]

    Трансформаторы с расширителем
    Расширитель ограничивает контакт масла с воздухом и компенсирует избыточное давление, что сокращает недостатки предыдущей конструкции. Тем не менее, диэлектрик поглощает влагу и непрерывно окисляется. В такой системе дополнительно применяют воздухоосушитель, благодаря чему уменьшается окисление масла, но возникает необходимость регулярного технического обслуживания.

    [Перевод Интент]

     


    Расширитель трансформатора
    Расширитель служит для локализации (компенсации) колебаний уровня масла в трансформаторе при изменении температуры. Кроме того, он уменьшает площадь соприкосновения с воздухом открытой поверхности масла и, следовательно, защищает масло от преждевременного окисления кислородом. Расширитель представляет собой металлический цилиндр, соединенный с баком трубопроводом. Существуют герметизированные трансформаторы с азотной защитой, у которых пространство между поверхностью масла и верхней стенкой расширителя заполнено азотом. Расширители устанавливают на трансформаторах напряжением 6 кВ и выше, мощностью 25 кВ-А и более. Объем расширителя выбирают таким, чтобы при всех режимах работы трансформатора от отключенного состояния до номинальной нагрузки и при колебаниях температуры окружающего воздуха от —45 до +40°С в нем было масло (обычно 8—10% объема масла, находящегося в трансформаторе).
    На рис. показан расширитель, устанавливаемый на трансформаторах III габарита. При нагревании масло из бака трансформатора по трубе, соединяющей его с патрубком 7, вытесняется в расширитель; при снижении температуры оно поступает обратно в бак. На торцовой стенке корпуса 2 расширителя установлен маслоуказатель 1 и нанесены краской три горизонтальные черты с контрольными цифрами: —45, +15 и +40°С. Это означает, что в неработающем трансформаторе уровни масла, отмеченные черточками, должны соответствовать указанным температурам окружающего воздуха. Другая торцовая стенка корпуса крепится болтами на маслоуплотняющей прокладке. Через разъем производят чистку и окраску внутренней поверхности расширителя.

    0397
    Устройство расширителя трансформаторов III габарита

    Для сбора и удаления осадков и влаги со дна расширителя предназначен отстойник 10 с отверстием, закрываемым пробкой 9 и служащим также для слива масла из расширителя. Изменение в расширителе уровня масла, а следовательно, его объема компенсируется атмосферным воздухом, поступающим в расширитель из окружающей среды через осушитель, подсоединяемый к патрубку 6. Отверстие с пробкой 5 предназначено для заполнения расширителя маслом, кольца 3 — для подъема, патрубок 4 — для соединения с предохранительной трубой. Чтобы осадки не попадали в трансформатор со дна расширителя, конец патрубка 7 выступает внутри расширителя на 50—60 мм.
    Расширитель устанавливают немного выше уровня крышки 6 трансформатора с помощью опорных пластин 12, которые приварены к кронштейнам 11, закрепляемым на крышке болтами.

    [http://forca.ru/spravka/spravka/rasshiritel-transformatora.html]

    Недопустимые, нерекомендуемые

    Тематики

    Классификация

    >>>

    Обобщающие термины

    Синонимы

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > conservateur d'huile

  • 11 transformateur immergé dans l'huile

    1. масляный трансформатор

     

     

    масляный трансформатор
    Трансформатор с жидким диэлектриком, в котором основной изолирующей средой и теплоносителем служит трансформаторное масло
    [ ГОСТ 16110-82]


    масляный трансформатор
    Трансформатор, магнитная система и обмотки которого погружены в масло
    (МЭС 421-01-14)
    [ ГОСТ 30830-2002]

    EN

    oil-immersed type transformer
    a transformer of which the magnetic circuit and windings are immersed in oi
    [IEV number 421-01-14]

    FR

    transformateur immergé dans l'huile
    transformateur dont le circuit magnétique et les enroulements sont immergés dans l'huile
    [IEV number 421-01-14]

    Oil transformers
    The magnetic circuit and the windings are immersed in a liquid dielectric that provides insulation and evacuates the heat losses of the transformer.
    This liquid expands according to the load and the ambient temperature. PCBs and TCBs are now prohibited and mineral oil is generally used. It is flammable and requires protective measures against the risks of fire, explosion and pollution.

    The most commonly used protective measures are the DGPT or the DGPT2: Gas, Pressure and Temperature sensor with 1 or 2 sensing levels on the temperature. This system cuts off the LV load (1st level) then the HV supply (2nd level) when there is a fault inside the transformer. A holding tank is used to recover all the liquid dielectric.

    Of the four types of immersed transformer: free breathing transformers, gas cushion transformers, transformers with expansion tank and transformers with integral filling, only the latter are currently installed.

    [Legrand]

    Масляные трансформаторы
    Магнитная система и обмотки трансформатора погружены в жидкий диэлектрик, служащий изоляцией и теплоносителем.
    Жидкий диэлектрик изменяет свой объем в соответствии с нагрузкой трансформатора и температурой окружающей среды. Поскольку в настоящее время применение полихлорированных дифенилов и тетрахлорбифенилов запрещено, то в основном используют минеральное масло. Оно огнеопасно, поэтому необходимо принимать меры против возникновения пожара, взрыва и загрязнения окружающей среды.

    Как правило, применяются системы DGPT (одноуровневые системы, использующие датчики газа, давления и температуры) или DGPT2 – двухуровневые системы.
    В случае возникновения аномального состояния трансформатора данные системы отключают нагрузку цепей низшего напряжения (первый уровень защиты), а затем питание обмотки высшего напряжения (второй уровень защиты). Активная часть трансформатора находится в баке и полностью покрыта жидким диэлектриком.

    Существует четыре типа масляных трансформаторов: трансформаторы с системой свободного дыхания, трансформаторы с газовой подушкой между зеркалом масла и крышкой трансформатора, трансформаторы с расширительным баком и трансформаторы с гофрированным баком. В настоящее время применяют только трансформаторы последнего типа

    [Интент]

    0375
    [http://www.ramo-chelny.ru/konschasti.html]

    Масляный трансформатор:

    1. Шихтованный магнитопровод
    2. Обмотка низшего напряжения
    3. Обмотка высшего напряжения
    4. Трубчатый бак
    5. Термометр
    6. Переключатель регулировочных отводов обмотки высшего напряжения
    7. Ввод (проходной изолятор) обмотки низшего напряжения
    8. Ввод (проходной изолятор) обмотки высшего напряжения
    9. Расширительный бак

    0376
    [http://transfcomplect.narod.ru/transformator.html]

    Тематики

    Классификация

    >>>

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > transformateur immergé dans l'huile

  • 12 transformateur de puissance

    1. силовой трансформатор

     

     

    силовой трансформатор
    Трансформатор, предназначенный для преобразования электрической энергии в электрических сетях и в установках, предназначенных для приема и использования электрической энергии.
    Примечание. К силовым относятся трансформаторы трехфазные и многофазные мощностью 6,3 кВ•А и более, однофазные мощностью 5 кВ•А и более.
    [ ГОСТ 16110-82]


    силовой трансформатор
    Статическое устройство, имеющее две или более обмотки, предназначенное для преобразования посредством электромагнитной индукции одной или нескольких систем переменного напряжения и тока в одну или несколько других систем переменного напряжения и тока, имеющих обычно другие значения при той же частоте, с целью передачи мощности
    (МЭС 421-01-01).
    [ ГОСТ 30830-2002]

    EN

    power transformer
    a static piece of apparatus with two or more windings which, by electromagnetic induction, transforms a system of alternating voltage and current into another system of voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power
    [IEV number 421-01-01]

    FR

    transformateur de puissance
    appareil statique à induction électromagnétique, à deux enroulements ou plus, destiné à transformer un système de tension(s) et courants(s) alternatifs en un autre système de tension(s) et courant(s) alternatifs, de valeurs généralement différentes et de même fréquence, en vue de transférer une puissance électrique
    [IEV number 421-01-01]

     

    Силовые трансформаторы, установленные на электростанциях и подстанциях, предназначены для преобразования электроэнергии с одного напряжения на другое. Наибольшее распространение получили трехфазные трансформаторы, так как потери в них на 12—15% ниже, а расход активных материалов и стоимость на 20—25% меньше, чем в группе трех однофазных трансформаторов такой же суммарной мощности.

    Трехфазные трансформаторы на напряжение 220 кВ изготовляют мощностью до 1000 MBА, на 330 кВ - 1250 МВА, на 500 кВ - 1000 МВА. Удельная единичная мощность трансформаторов ограничивается массой, размерами, условиями транспортировки.

    Однофазные трансформаторы применяются, если невозможно изготовление трехфазных трансформаторов необходимой мощности или затруднена их транспортировка. Наибольшая мощность группы однофазных трансформаторов напряжением 500 кВ — 3 * 533 МВА, напряжением 750 кВ - 3 * 417 МВА, напряжением 1150 кВ - 3 * 667 MBA.

    По количеству обмоток различного напряжения на каждую фазу трансформаторы разделяются на двухобмоточные и трехобмоточные. Кроме того, обмотки одного и того же напряжения, обычно низшего, могут состоять из двух и более параллельных ветвей, изолированных друг от друга и от заземленных частей. Такие трансформаторы называются трансформаторами с расщепленными обмотками. Обмотки высшего, среднего и низшего напряжения принято сокращенно обозначать соответственно ВН, СН, НН.

    Трансформаторы с расщепленными обмотками НН обеспечивают возможность присоединения нескольких генераторов к одному повышающему трансформатору. Такие укрупненные энергоблоки позволяют упростить схему РУ 330—500 кВ. Широкое распространение трансформаторы с расщепленной обмоткой НН получили в схемах питания собственных нужд крупных ТЭС с блоками 200-1200 МВт, а также на понижающих подстанциях с целью ограничения токов КЗ.

    [http://forca.ru/info/spravka/silovye-transformatory.html]

    Устройство и элементы конструкции силовых трансформаторов

    Силовые трансформаторы (автотрансформаторы) в зависимости от мощности и напряжения условно делят на восемь габаритов. Так, например, к нулевому габариту относят трансформаторы мощностью до 5 кВ-А включительно, мощностью свыше 5 кВ-А — до 100 кВ-А напряжением до 35 кВ (включительно) к I габариту, выше 100 до 1000 — ко II, выше 1000 до 6300 — к III; выше 6300 — к IV, а напряжением выше 35 до 110 кВ (включительно) и мощностью до 32 000 кВ-А — к V габариту. Для отличия по конструктивным признакам, назначению, мощности и напряжению их подразделяют на типы.
    Каждому типу трансформаторов присваивают обозначение, состоящее из букв и цифр. Буквы в типах масляных и сухих трансформаторов обозначают: О — однофазный, Т — трехфазный, Н — регулирование напряжения под нагрузкой, Р — с расщепленными обмотками; по видам охлаждения: С — естественно-воздушное, М — естественная циркуляция воздуха и масла, Д — принудительная циркуляция воздуха и естественная циркуляция масла, ДЦ — принудительная циркуляция воздуха и масла, MB — принудительная циркуляция воды и естественная циркуляция масла, Ц— принудительная циркуляция воды и масла. Вторичное употребление буква С в обозначении типа показывает, что трансформатор трехобмоточный.

    0398

    Устройство силового масляного трансформатора мощностью 1000—6300 кВ-А класса напряжения 35 кВ:

    1 — бак, 2 — вентиль, 3 — болт заземления, 4 — термосифонный фильтр, 5 — радиатор, 6 — переключатель, 7 — расширитель, 8 — маслоуказатель, 9—воздухоосушитель, 10 — выхлопная труба, 11 — газовое реле, 12 — ввод ВН, 13 — привод переключающего устройства, 14 — ввод НН, 15 — подъемный рым, 16 — отвод НН, 17 — остов, 18 — отвод ВН, 19 — ярмовая балка остова (верхняя и нижняя), 20 — регулировочные ответвления обмоток ВН, 21 — обмотка ВН (внутри НН), 22 — каток тележки

    Составными частями масляного трансформатора являются: остов обмотки, переключающее устройство, вводы, отводы, изоляция, бак, охладители, защитные и контрольно-измерительные и вспомогательные устройства.
    Конструкция, включающая в собранном виде остов трансформатора, обмотки с их изоляцией, отводы, части регулирующего устройства, а также все детали, служащие для их механического соединения, называется активной частью трансформатора.

    [http://forca.ru/spravka/spravka/ustroystvo-i-elementy-konstrukcii-silovyh-transformatorov.html]


    Тематики

    Классификация

    >>>

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > transformateur de puissance

  • 13 protection de masse

    1. защита от тока утечки на корпус

     

    защита от тока утечки на корпус
    Защита, входной воздействующей величиной которой является ток, протекающий через соединение, связывающее корпус установки с землей.
    Пример: защита трансформатора от тока утечки на бак.
    [Разработка типовых структурных схем микропроцессорных устройств РЗА на объектах ОАО "ФКС ЕЭС". Пояснительная записка. Новосибирск 2006 г.]

    EN

    frame leakage protection
    case ground protection (US)
    frame ground protection (US)

    protection in which the input energizing quantity is a current flowing through the path connecting the framework of the stated equipment in the protected section to earth
    Example: A frame leakage protection of a transformer tank.
    [ IEV ref 448-14-21]

    FR

    protection de masse
    protection dont la grandeur d'alimentation est un courant circulant dans la connexion reliant à la terre la structure du matériel considéré, dans la section protégée
    Exemple: Protection de masse d'une cuve de transformateur.
    [ IEV ref 448-14-21]

    Тематики

    EN

    DE

    • Gestell-Erdschlussschutz, m
    • Kessel-Erdschlussschutz, m

    FR

    Франко-русский словарь нормативно-технической терминологии > protection de masse

См. также в других словарях:

  • бак трансформатора — Бак, в котором размещается активная часть трансформатора или трансформаторного агрегата с жидким диэлектриком, газо или кварценаполненного [ГОСТ 16110 82] EN tank the vessel in which the core, yoke and windings of a transformer or reactor are… …   Справочник технического переводчика

  • Бак трансформатора — 6.6. Бак трансформатора Бак, в котором размещается активная часть трансформатора или трансформаторного агрегата с жидким диэлектриком, газо или кварценаполненного Источник: ГОСТ 16110 82: Трансформаторы силовые. Термины и определения оригинал… …   Словарь-справочник терминов нормативно-технической документации

  • Бак трансформатора — English: Transformer tank Бак, в котором размещается активная часть трансформатора или трансформаторного агрегата с жидким диэлектриком, газо или кварценаполненного (по ГОСТ 16110 82 СТ СЭВ 1103 78) Источник: Термины и определения в… …   Строительный словарь

  • расширительный бак трансформатора — — [Я.Н.Лугинский, М.С.Фези Жилинская, Ю.С.Кабиров. Англо русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.] Тематики электротехника, основные понятия EN expansion tank of transformer …   Справочник технического переводчика

  • бак колокольного типа — Бак, имеющий вблизи дна разъем, позволяющий отделить и поднять верхнюю часть бака без подъема активной части трансформатора [ГОСТ 16110 82] Тематики трансформатор Классификация >>> Обобщающие термины часть трансформатора …   Справочник технического переводчика

  • Бак колокольного типа — 6.7. Бак колокольного типа Бак, имеющий вблизи дна разъем, позволяющий отделить и поднять верхнюю часть бака без подъема активной части трансформатора Источник: ГОСТ 16110 82: Трансформаторы силовые. Термины и определения оригинал документа …   Словарь-справочник терминов нормативно-технической документации

  • система охлаждения (трансформатора) — система охлаждения Совокупность теплообменников или элементов системы охлаждения, устройств, предназначенных для ускорения движения теплоносителя и (или) охлаждающей среды, контрольных и измерительных приборов, служащая для отвода тепла,… …   Справочник технического переводчика

  • радиатор трансформатора — Теплообменник, в котором происходит передача тепла от теплоносителя, заполняющего бак трансформатора и движущегося путем естественной конвекции, воздуху, охлаждающему трансформатор [ГОСТ 16110 82] Тематики трансформатор Классификация >>> …   Справочник технического переводчика

  • Радиатор трансформатора — 6.26. Радиатор трансформатора Теплообменник, в котором происходит передача тепла от теплоносителя, заполняющего бак трансформатора и движущегося путем естественной конвекции, воздуху, охлаждающему трансформатор Источник: ГОСТ 16110 82:… …   Словарь-справочник терминов нормативно-технической документации

  • Регулирование напряжения трансформатора — Силовой трансформатор Регулирование напряжения трансформатора  изменение числа витков обмотки трансформатора. Применяется для поддержания нормального уровня напряже …   Википедия

  • защита (трансформатора) от замыканий на бак — — [Я.Н.Лугинский, М.С.Фези Жилинская, Ю.С.Кабиров. Англо русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.] Тематики электротехника, основные понятия EN tank ground protection …   Справочник технического переводчика

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»