-
1 длительный допустимый ток
- courant permanent admissible, m
- courant admissible, m
(длительный) допустимый ток
Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
[ ГОСТ Р МЭК 60050-826-2009]
Этот ток обозначают IZ
[ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]EN
(continuous) current-carrying capacity
ampacity (US)
maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
[IEV number 826-11-13]
ampacity
The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
[National Electrical Cod]FR
courant (permanent) admissible, m
valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
[IEV number 826-11-13]Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:
- its insulation temperature rating;
- conductor electrical properties for current;
- frequency, in the case of alternating currents;
- ability to dissipate heat, which depends on cable geometry and its surroundings;
- ambient temperature.
Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.
The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.
In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.
Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.
The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.
For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.
Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.
When designing an electrical system, one will normally need to know the current rating for the following:- Wires
- Printed Circuit Board traces, where included
- Fuses
- Circuit breakers
- All or nearly all components used
Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.
[http://en.wikipedia.org/wiki/Ampacity]
Тематики
- электротехника, основные понятия
Синонимы
EN
DE
- Dauerstrombelastbarkeit, f
- Strombelastbarkeit, f
FR
- courant admissible, m
- courant permanent admissible, m
Русско-французский словарь нормативно-технической терминологии > длительный допустимый ток
-
2 максимальная толщина шва
максимальная толщина шва
Значение, измеряемое от самой глубокой точки проплавления углового шва или крайней точки корня стыкового шва до наивысшей точки выпуклости шва.
Примечание
Измерение обычно проводят по поперечному сечению шва.
[ ГОСТ Р ИСО 17659-2009] [ISO 17659:2002]EN
maximum throat thickness
Dimension measured from the deepest point of the penetration in fillet welds or the extremity of the root run in butt welds to the highest point of the excess weld metal.
Note
This is usually measured from a cross-section.
[ ГОСТ Р ИСО 17659-2009] [ISO 17659:2002]FR
gorge totale (soudures d'angle)
épaisseur totale (soudures bout а bout)
Soudures d'angle distance mesurée entre le point le plus bas de la pénétration et le point le plus haut de la surépaisseur soudures bout а bout distance mesurée entre le point le plus bas de la passe de fond et le point le plus haut de la surépaisseur.
Note
Cette distance est habituellement mesurée sur une coupe transversale.
[ ГОСТ Р ИСО 17659-2009] [ISO 17659:2002]Тематики
- сварка, резка, пайка
EN
FR
Русско-французский словарь нормативно-технической терминологии > максимальная толщина шва
См. также в других словарях:
Run rate — In cricket, the run rate (RR), or runs per over (RPO) is the number of runs a batsman (or the batting side) scores in an over of 6 balls. It includes all runs, even the so called extras awarded due to errors by the bowler. Without extras, the… … Wikipedia
Maximum Ride — Maximum Ride: The Angel Experiment Maximum Ride: School s Out Forever Maximum Ride: Saving the World and Other Extreme Sports Maximum Ride: The Final Warning MAX: A Maximum Ride Novel Fang: A Maximum Ride Novel Angel: A Maximum Ride Novel… … Wikipedia
Maximum parsimony — Maximum parsimony, often simply referred to as parsimony, is a non parametric statistical method commonly used in computational phylogenetics for estimating phylogenies. Under maximum parsimony, the preferred phylogenetic tree is the tree that… … Wikipedia
Maximum Ride: School's Out Forever — Maximum Ride: School s Out Forever … Wikipedia
Maximum Ride: The Angel Experiment — Maximum Ride: The Angel Experiment … Wikipedia
Run length limited — or RLL coding is a technique that is used to store data on recordable media. Specifically, RLL prevents long stretches of repeated bits from causing the signal recorded on media to not change for an excessive period, by modulating the data. RLL… … Wikipedia
Maximum Ride: The Final Warning — Maximum Ride: The Final Warning … Wikipedia
Maximum Exposure — Format Reality television Starring Cam Brainard Country of origin … Wikipedia
Maximum Groove — Maximum II Studio album by MAX Released December 2, 1998 … Wikipedia
Maximum Drive — Genre Game show Presented by Joe Fowler with Brian Vermeire Mercedes Colon Country of origin … Wikipedia
Maximum (MAX album) — Maximum Studio album by MAX Released December 11, 1996 … Wikipedia