21 коэффициент циклической токовой нагрузки (кабелей)
коэффициент циклической токовой нагрузки (кабелей)
Коэффициент, на который может быть умножен номинальный ток установившегося режима, соответствующий коэффициенту нагрузки 100 %, для получения допустимого пикового значения тока в течение суточного цикла, при котором температура токопроводящей жилы в течение этого цикла достигает, но не превышает максимально допустимое значение
[IEV number 461-23-02]EN
cyclic rating factor
factor by which the permissible steady-state rated current corresponding to a 100 % load factor may be multiplied to obtain the permissible peak value of current during a daily cycle such that the conductor attains, but does not exceed, the maximum rated temperature during the cycle
[IEV number 461-23-02]FR
facteur de régime cyclique
facteur par lequel le courant assigné admissible en régime permanent, correspondant à un facteur de charge 100 %, peut être multiplié pour obtenir la valeur de pointe du courant au cours d'un cycle journalier, de sorte qu'au cours de ce cycle, l'âme atteigne sans la dépasser la température assignée maximale
[IEV number 461-23-02]Тематики
- кабели, провода...
EN
DE
FR
Русско-французский словарь нормативно-технической терминологии > коэффициент циклической токовой нагрузки (кабелей)
-
22 максимальная нагрузка постоянным током (напряжением) пьезоэлектрического (электромеханического) фильтра
- charge с. с. maximale
максимальная нагрузка постоянным током (напряжением) пьезоэлектрического (электромеханического) фильтра (())
Максимальное допустимое значение постоянного тока (напряжения), поступающего на вход пьезоэлектрического (электромеханического) фильтра, при котором его электрические параметры и характеристики остаются в заданных пределах.
[ ГОСТ 18670-84]Тематики
EN
- maximum d. с. load
FR
- charge с. с. maximale
Русско-французский словарь нормативно-технической терминологии > максимальная нагрузка постоянным током (напряжением) пьезоэлектрического (электромеханического) фильтра
-
23 максимально допустимая удельная нагрузка на подшипник
максимально допустимая удельная нагрузка на подшипник
Предельное значение удельной нагрузки на подшипник, превышение которой может привести к разрушению подшипника.
[ ГОСТ ИСО 4378-4-2001]Тематики
Обобщающие термины
EN
FR
Русско-французский словарь нормативно-технической терминологии > максимально допустимая удельная нагрузка на подшипник
-
24 полная селективность
полная селективность
Селективность по сверхтокам, когда при последовательном соединении двух аппаратов защиты от сверхтоков аппарат со стороны нагрузки осуществляет защиту без срабатывания второго защитного аппарата.
[ ГОСТ Р 50030. 2-99 ( МЭК 60947-2-98)]EN
total discrimination (total selectivity)
over-current discrimination where, in the presence of two or more over-current protective devices in series, the protective device on the load side effects the protection without causing the other protective devices to operate
[IEC 61892-2, ed. 1.0 (2005-03)]FR
sélectivité totale
sélectivité lors d’une surintensité dans laquelle, en présence de deux dispositifs de protection à maximum de courant placés en série, le dispositif de protection aval assure la protection sans provoquer le fonctionnement de l’autre dispositif de protection
[IEC 60947-2, ed. 4.0 (2006-05)]Тематики
EN
FR
Русско-французский словарь нормативно-технической терминологии > полная селективность
-
25 предельный ток селективности
предельный ток селективности Is Токовая координата точки пересечения полной время-токовой характеристики защитного аппарата со стороны нагрузки и преддуговой (для плавких предохранителей) время-токовой характеристики или время-токовой характеристики расцепления второго защитного аппарата.
Предельный ток селективности (см. рисунок А.1) — это предельное значение тока:- ниже которого при последовательном соединении двух аппаратов защиты от сверхтоков защитный аппарат со стороны нагрузки завершает операцию отключения, чтобы воспрепятствовать началу действия второго защитного аппарата (т. е. обеспечивается селективность);
- выше которого при последовательном соединении двух аппаратов защиты от сверхтоков защитный аппарат со стороны нагрузки может не успеть вовремя завершить операцию отключения, чтобы воспрепятствовать началу действия второго защитного аппарата (т. е. селективность не обеспечивается).
Is - предельный ток селективности;
Icu - номинальная предельная наибольшая отключающая способность;
А - преддуговая характеристика плавкого предохранителя;
В - рабочая характеристика плавкого предохранителя;
С - рабочая характеристика нетокоограничивающего выключателя (N) (время отключения/ток и I2t/ток) Примечания.
1. А считают нижним пределом, В и С - верхними пределами.
2. Недиабатическая зона для I2t показана пунктиром Рис. А1.
Координация по сверхтокам между автоматическим выключателем и предохранителем
или резервной защитой, осуществляемой предохранителем.
[ ГОСТ Р 50030. 2-99 ( МЭК 60947-2-98)]EN
selectivity-limit current
the current coordinate of the intersection between the maximum break time-current characteristic of the protective device on the load side and the pre-arcing (for fuses) or tripping (for residual current devices) time-current characteristic of the other protective device
[IEV number 442-05-60]FR
courant limite
coordonnée du courant de l'intersection entre la caractéristique de durée maximale de coupure temps-courant du dispositif de protection côté aval et la caractéristique temps-courant de pré-arc (pour les fusibles) ou de déclenchement (pour les dispositifs de coupure différentiels) de l'autre dispositif de protection.
[IEV number 442-05-60]Тематики
- аппарат, изделие, устройство...
- выключатель автоматический
Синонимы
- Is
EN
DE
FR
Русско-французский словарь нормативно-технической терминологии > предельный ток селективности
-
26 прямой пуск вращающегося электродвигателя
прямой пуск вращающегося электродвигателя
Пуск вращающегося электродвигателя путем непосредственного подключения его к питающей сети.
[ ГОСТ 27471-87]EN
direct-on-line starting
across-the-line starting (US)
the process of starting a motor by connecting it directly to the supply at rated voltage
[IEV number 411-52-15]FR
démarrage direct
mode de démarrage d'un moteur, consistant à lui appliquer directement sa pleine tension assignée
[IEV number 411-52-15]
Рис. ABB
Схема прямого пуска электродвигателяMagnetic only circuit-breaker - Автоматический выключатель с электромагнитным расцепителем
Contactor KL - Контактор KL
Thermal relay - Тепловое реле
Параллельные тексты EN-RU
Direct-on-line starting
Direct-on-line starting, which is often abbreviated as DOL, is perhaps the most traditional system and consists in connecting the motor directly to the supply network, thus carrying out starting at full voltage.Direct-on-line starting represents the simplest and the most economical system to start a squirrel-cage asynchronous motor and it is the most used.
As represented in Figure 5, it provides the direct connection to the supply network and therefore starting is carried out at full voltage and with constant frequency, developing a high starting torque with very reduced acceleration times.
The typical applications are relevant to small power motors also with full load starting.
These advantages are linked to some problems such as, for example, the high inrush current, which - in the first instants - can reach values of about 10 to 12 times the rated current, then can decrease to about 6 to 8 times the rated current and can persist to reach the maximum torque speed.The effects of such currents can be identified with the high electro-dynamical stresses on the motor connection cables and could affect also the windings of the motor itself; besides, the high inrush torques can cause violent accelerations which stress the transmission components (belts and joints) generating distribution problems with a reduction in the mechanical life of these elements.
Finally, also the possible electrical problems due to voltage drops on the supply line of the motor or of the connected equipment must be taken into consideration.
[ABB]Прямой пуск
Прямой пуск, который по-английски часто сокращенно обозначают как DOL, является, пожалуй наиболее распространенным способом пуска. Он заключается в непосредственном (т. е. прямом) подключении двигателя к питающей сети. Это означает, что пуск двигателя осуществляется при полном напряжении.Схема прямого пуска является наиболее простым, экономичным и чаще всего применяемым решением для электродвигателей с короткозамкнутым ротором.
Схема прямого подключения к сети представлена на рисунке 5. Пуск осуществляется при полном напряжении и постоянной частоте сети. Электродвигатель развивает высокий пусковой момент при коротком времени разгона.
Типичные области применения – маломощные электродвигатели, в том числе с пуском при полной нагрузке.
Однако, наряду с преимуществами имеются и определенные недостатки, например, бросок пускового тока, достигающий в первоначальный момент 10…12-кратного значения от номинального тока электродвигателя. Затем ток двигателя уменьшается примерно до 6…8-кратного значения номинального тока и будет держаться на этом уровне до тех пор, пока скорость двигателя не достигнет максимального значения.
Такое изменение тока оказывает значительное электродинамическое воздействие на кабель, подключенный к двигателю. Кроме того пусковой ток воздействует на обмотки двигателя. Высокий начальный пусковой момент может привести к значительному ускорению и следовательно к значительной нагрузке элементов привода (ремней, крепления узлов), что вызывает сокращение их срока службы.
И, наконец, следует принять во внимание возможное возникновение проблем, связанных с падением напряжения в линии питания двигателя и подключенного к этой линии оборудования.
[Перевод Интент]
Тематики
Синонимы
EN
- across-the-line starting (US)
- direct line starting
- direct operation of a motor
- direct starting
- direct-on-line starting
- DOL
- full voltage starter application
DE
FR
Русско-французский словарь нормативно-технической терминологии > прямой пуск вращающегося электродвигателя
-
27 частичная селективность
частичная селективность
Селективность по сверхтокам, когда при последовательном соединении двух аппаратов защиты от сверхтоков аппарат со стороны нагрузки осуществляет защиту до определенного уровня сверхтока без срабатывания второго защитного аппарата.
[ ГОСТ Р 50030. 2-99 ( МЭК 60947-2-98)]EN
partial discrimination (partial selectivity)
overcurrent discrimination where, in the presence of two overcurrent protective devices in series, the protective device on the load side effects the protection up to a given level of overcurrent, without causing the other protective device to operate
[IEC 60947-2, definition 2.17.3]FR
sélectivité partielle
sélectivité lors d'une surintensité dans laquelle, en présence de deux dispositifs de protection à maximum de courant placés en série, le dispositif de protection aval assure la protection jusqu'à un niveau donné de surintensité sans provoquer le fonctionnement de l'autre dispositif de protection
[IEC 60947-2, definition 2.17.3]Тематики
EN
FR
Русско-французский словарь нормативно-технической терминологии > частичная селективность
- 1
- 2
См. также в других словарях:
maximum load — maksimalioji apkrova statusas T sritis automatika atitikmenys: angl. maximum load; peak load vok. Höchslast, f; Höchstbelastung, f; Lastspitze, f; Spitzenbelastung, f; Spitzenlast, f rus. максимальная нагрузка, f; максимум нагрузки, m pranc.… … Automatikos terminų žodynas
maximum load — didžiausiasis krūvis statusas T sritis Kūno kultūra ir sportas apibrėžtis Didžiausias krūvis, kurį sportininkas gali pakelti, nepadarydamas žalos savo organizmui. atitikmenys: angl. maximum load; repetition maximum vok. Maximalbelastung, f rus.… … Sporto terminų žodynas
maximum load — didžiausiasis krūvis statusas T sritis Kūno kultūra ir sportas apibrėžtis Didžiausiasis krūvis, kurį gali pakelti raumuo ar raumenų grupė vienu bandymu. atitikmenys: angl. maximum load; repetition maximum vok. Maximalbelastung, f rus.… … Sporto terminų žodynas
maximum load — didžiausiasis krūvis statusas T sritis Kūno kultūra ir sportas apibrėžtis Ugdomieji fiziniai krūviai, labai veikiantys pagrindines funkcines sportininko organizmo sistemas ir sukeliantys stiprų nuovargį. Didžiausiasis krūvis gali turėti integralų … Sporto terminų žodynas
Load regulation — is the capability to maintain a constant voltage (or current) level on the output channel of a power supply despite changes in load [cite web|title=Line and Load Regulation for Programmable DC Power Supplies and Precision DC Sources Developer… … Wikipedia
Load factor (aerodynamics) — Load factor is the ratio of the lift on an aircraft to the weight of the aircraft.Clancy, L.J., Aerodynamics , section 5.22] Hurt, H.H., Aerodynamics for Naval Aviators , page 37] The load factor is expressed in multiples of g where one g… … Wikipedia
Load Factor — The ratio of average energy demand (load) to maximum demand (peak load) during a specific period. The ratio of the average load supplied to the peak or maximum load during a designated period. Load factor, in percent, also may be derived by… … Energy terms
load — {{Roman}}I.{{/Roman}} noun ADJECTIVE ▪ heavy, light ▪ He has a heavy teaching load this year. ▪ full ▪ The plane took off with a full load. ▪ … Collocations dictionary
load — A sales charge paid by an investor in some mutual fund shares or annuities. The sales charge may be a front end charge, a back end charge, or a 12b 1 charge. Also, an expression used to describe a mutual fund that imposes sales charges on… … Financial and business terms
maximum — 01. Currently, the [maximum] number of students in our classes in the English Language Program is 18. 02. The cost to repair your car should be no more than $500, [maximum]. 03. Ching wen obtained a score of 89 out of a [maximum] of 110 on the… … Grammatical examples in English
maximum de charge — maksimalioji apkrova statusas T sritis automatika atitikmenys: angl. maximum load; peak load vok. Höchslast, f; Höchstbelastung, f; Lastspitze, f; Spitzenbelastung, f; Spitzenlast, f rus. максимальная нагрузка, f; максимум нагрузки, m pranc.… … Automatikos terminų žodynas