Перевод: со всех языков на русский

с русского на все языки

made-up+circuit

  • 41 disjoncteur limiteur de courant

    1. токоограничивающий автоматический выключатель

     

    токоограничивающий автоматический выключатель
    Выключатель с чрезвычайно малым временем отключения, в течение которого ток короткого замыкания не успевает достичь своего максимального значения.
    [МЭК 60947-1]

    En

    current-limiting circuit breaker
    Circuit-breaker with a break-time short enough to prevent the short-circuit current reaching its otherwise attainable peak value.
    [< size="2">IEC 60077-3, ed. 1.0 (2001-12)]

     
     

    Circuit-breaker that, within a specified range of current, prevents the let-through current reaching the prospective peak value and which limits the let-through energy (I2t) to a value less than the let-through energy of a half-cycle wave of the symmetrical prospective current
    NOTE 1 - Reference may be made to either the symmetrical or asymmetrical prospective peak value of let-through current.
    NOTE 2 - The let-through current is also referred to as the cut-off current (see IEV 441-17-12).
    NOTE 3 - Templates for the graphical representation of the cut-off current characteristic and the let-through energy characteristic are given in Figures K.2 to K.5 and examples of the use of the templates in Figures K.6 and K.7.
    [IEC 60947-2, ed. 4.0, amd. 1 (2009-01)]

    Fr

    disjoncteur limiteur de courant
    Disjoncteur dont la durée de coupure est particulièrement brève en vue d’obtenir que le courant de court-circuit ne puisse atteindre son amplitude maximale
    [< size="2">IEC 60077-3, ed. 1.0 (2001-12)]


    Disjoncteur qui, à l'intérieur d'un domaine de courant spécifié, empêche le courant coupé limité d'atteindre la valeur crête présumée et qui limite l'énergie limitée (I2t) à une valeur inférieure à l'énergie limitée d'une demi-période du courant présumé symétrique
    NOTE 1 Il peut être fait référence à la valeur crête présumée symétrique ou assymétrique du courant coupé limité.
    NOTE 2 Le courant coupé limité (let-through current) est aussi nommé "cut-off current" (voir VEI 441-17-12).
    NOTE 3 Les modèles de représentation graphique des caractéristiques de courant coupé limité et d'énergie limitée sont illustrés dans les Figures K.2 à K.5 et les exemples d'utilisation des modèles dans les Figures K.6 et K.7.
    [IEC 60947-2, ed. 4.0, amd. 1 (2009-01)]

    Токоограничивающий автоматический выключатель имеет чрезвычайно малое время отключения, в течение которого ток КЗ не успевает достичь максимального значения.
    Токоограничивающие автоматические выключатели ограничивают ток
    КЗ с помощью быстрого введения в цепь дополнительного сопротивления электрической дуги (в первый же полупериод, до того, как ток КЗ значительно возрастет) и последующего быстрого отключения КЗ, при этом ток КЗ не достигает ожидаемого расчетного максимального значения. Токоограничение начинается с некоторого значения тока, определяемого характеристикой токоогранияения.
    В токоограничивающих автоматических выключателях при больших ожидаемых токах КЗ контакты, сразу же отбрасываются электродинамическими силами, вво
    дя в цепь сопротивление дуги, и затем уже не соприкасаются, так как своевременно срабатывает электромагнитный расцепитель.
    При малых токах
    КЗ контакты не отбрасываются, а отключение производится электромагнитным расцепителем.
    [А.В.Беляев. Выбор аппаратуры, защит и кабелей в сетях 0,4 кВ. - Л.: Энергоатомиздат. 1988.]

    Тематики

    Классификация

    >>>

    Обобщающие термины

    EN

    DE

    FR

    Франко-русский словарь нормативно-технической терминологии > disjoncteur limiteur de courant

  • 42 Trennschalter

    1. разъединитель

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Немецко-русский словарь нормативно-технической терминологии > Trennschalter

  • 43 Schaltanlage

    1. Электрическое распределительное устройство
    2. распределительное устройство

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    Немецко-русский словарь нормативно-технической терминологии > Schaltanlage

  • 44 Schaltstation

    1. распределительное устройство
    2. (электрическое) распределительное устройство

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    3 (электрическое) распределительное устройство; РУ

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.

    Примечание. К устройствам управления относятся аппараты и связывающие их элементы, обеспечивающие контроль, измерение, сигнализацию и выполнение команд

    605-01-02**

    de Schaltstation

    en switching substation

    fr poste de sectionnement, poste de coupure

    Источник: ГОСТ 24291-90: Электрическая часть электростанции и электрической сети. Термины и определения оригинал документа

    Немецко-русский словарь нормативно-технической терминологии > Schaltstation

  • 45 strombegrenzender Leistungsschalter

    1. токоограничивающий автоматический выключатель

     

    токоограничивающий автоматический выключатель
    Выключатель с чрезвычайно малым временем отключения, в течение которого ток короткого замыкания не успевает достичь своего максимального значения.
    [МЭК 60947-1]

    En

    current-limiting circuit breaker
    Circuit-breaker with a break-time short enough to prevent the short-circuit current reaching its otherwise attainable peak value.
    [< size="2">IEC 60077-3, ed. 1.0 (2001-12)]

     
     

    Circuit-breaker that, within a specified range of current, prevents the let-through current reaching the prospective peak value and which limits the let-through energy (I2t) to a value less than the let-through energy of a half-cycle wave of the symmetrical prospective current
    NOTE 1 - Reference may be made to either the symmetrical or asymmetrical prospective peak value of let-through current.
    NOTE 2 - The let-through current is also referred to as the cut-off current (see IEV 441-17-12).
    NOTE 3 - Templates for the graphical representation of the cut-off current characteristic and the let-through energy characteristic are given in Figures K.2 to K.5 and examples of the use of the templates in Figures K.6 and K.7.
    [IEC 60947-2, ed. 4.0, amd. 1 (2009-01)]

    Fr

    disjoncteur limiteur de courant
    Disjoncteur dont la durée de coupure est particulièrement brève en vue d’obtenir que le courant de court-circuit ne puisse atteindre son amplitude maximale
    [< size="2">IEC 60077-3, ed. 1.0 (2001-12)]


    Disjoncteur qui, à l'intérieur d'un domaine de courant spécifié, empêche le courant coupé limité d'atteindre la valeur crête présumée et qui limite l'énergie limitée (I2t) à une valeur inférieure à l'énergie limitée d'une demi-période du courant présumé symétrique
    NOTE 1 Il peut être fait référence à la valeur crête présumée symétrique ou assymétrique du courant coupé limité.
    NOTE 2 Le courant coupé limité (let-through current) est aussi nommé "cut-off current" (voir VEI 441-17-12).
    NOTE 3 Les modèles de représentation graphique des caractéristiques de courant coupé limité et d'énergie limitée sont illustrés dans les Figures K.2 à K.5 et les exemples d'utilisation des modèles dans les Figures K.6 et K.7.
    [IEC 60947-2, ed. 4.0, amd. 1 (2009-01)]

    Токоограничивающий автоматический выключатель имеет чрезвычайно малое время отключения, в течение которого ток КЗ не успевает достичь максимального значения.
    Токоограничивающие автоматические выключатели ограничивают ток
    КЗ с помощью быстрого введения в цепь дополнительного сопротивления электрической дуги (в первый же полупериод, до того, как ток КЗ значительно возрастет) и последующего быстрого отключения КЗ, при этом ток КЗ не достигает ожидаемого расчетного максимального значения. Токоограничение начинается с некоторого значения тока, определяемого характеристикой токоогранияения.
    В токоограничивающих автоматических выключателях при больших ожидаемых токах КЗ контакты, сразу же отбрасываются электродинамическими силами, вво
    дя в цепь сопротивление дуги, и затем уже не соприкасаются, так как своевременно срабатывает электромагнитный расцепитель.
    При малых токах
    КЗ контакты не отбрасываются, а отключение производится электромагнитным расцепителем.
    [А.В.Беляев. Выбор аппаратуры, защит и кабелей в сетях 0,4 кВ. - Л.: Энергоатомиздат. 1988.]

    Тематики

    Классификация

    >>>

    Обобщающие термины

    EN

    DE

    FR

    Немецко-русский словарь нормативно-технической терминологии > strombegrenzender Leistungsschalter

  • 46 gear

    1. распределительный щит
    2. распределительное устройство
    3. оборудование
    4. инструменты
    5. входить в сцепление
    6. аппаратура

     

    аппаратура
    -
    [Интент]

    FR


    Тематики

    • аппарат, изделие, устройство...

    EN

     

    входить в сцепление
    приводить в движение механизм


    [ http://slovarionline.ru/anglo_russkiy_slovar_neftegazovoy_promyishlennosti/]

    Тематики

    Синонимы

    EN

     

    оборудование
    Совокупность связанных между собой частей или устройств, из которых по крайней мере одно движется, а также элементы привода, управления и энергетические узлы, которые предназначены для определенного применения, в частности для обработки, производства, перемещения или упаковки материала. К термину «оборудование» относят также машину и совокупность машин, которые так устроены и управляемы, что они функционируют как единое целое для достижения одной и той же цели.
    [ГОСТ ЕН 1070-2003]

    оборудование
    -

    [IEV number 151-11-25 ]

    оборудование
    Оснащение, материалы, приспособления, устройства, механизмы, приборы, инструменты и другие принадлежности, используемые в качестве частей электрической установки или в соединении с ней.
    [ ГОСТ Р МЭК 60204-1-2007]

    EN

    equipment
    single apparatus or set of devices or apparatuses, or the set of main devices of an installation, or all devices necessary to perform a specific task
    NOTE – Examples of equipment are a power transformer, the equipment of a substation, measuring equipment.
    [IEV number 151-11-25 ]

    equipment
    material, fittings, devices, components, appliances, fixtures, apparatus, and the like used as part of, or in connection with, the electrical equipment of machines
    [IEC 60204-1-2006]

    FR

    équipement, m
    matériel, m
    appareil unique ou ensemble de dispositifs ou appareils, ou ensemble des dispositifs principaux d'une installation, ou ensemble des dispositifs nécessaires à l'accomplissement d'une tâche particulière
    NOTE – Des exemples d’équipement ou de matériel sont un transformateur de puissance, l’équipement d’une sous-station, un équipement de mesure.
    [IEV number 151-11-25]

    Тематики

    EN

    DE

    FR

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

     

    распределительный щит
    Комплектное устройство, содержащее различную коммутационную аппаратуру, соединенное с одной или более отходящими электрическими цепями, питающееся от одной или более входящих цепей, вместе с зажимами для присоединения нейтральных и защитных проводников.
    [ ГОСТ Р МЭК 60050-826-2009]

    щит распределительный
    Электротехническое устройство, объединяющее коммутационную, регулирующую и защитную аппаратуру, а также контрольно-измерительные и сигнальные приборы
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    распределительный щит

    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    EN

    distribution board
    assembly containing different types of switchgear and controlgear associated with one or more outgoing electric circuits fed from one or more incoming electric circuits, together with terminals for the neutral and protective conductors.
    [IEV number 826-16-08]

    FR

    tableau de répartition, m
    ensemble comportant différents types d'appareillage associés à un ou plusieurs circuits électriques de départ alimentés par un ou plusieurs circuits électriques d'arrivée, ainsi que des bornes pour les conducteurs neutre et de protection.
    [IEV number 826-16-08]

    Параллельные тексты EN-RU

    Distribution switchboards, including the Main LV Switchboard (MLVS), are critical to the dependability of an electrical installation. They must comply with well-defined standards governing the design and construction of LV switchgear assemblies

    A distribution switchboard is the point at which an incoming-power supply divides into separate circuits, each of which is controlled and protected by the fuses or switchgear of the switchboard. A distribution switchboard is divided into a number of functional units, each comprising all the electrical and mechanical elements that contribute to the fulfilment of a given function. It represents a key link in the dependability chain.

    Consequently, the type of distribution switchboard must be perfectly adapted to its application. Its design and construction must comply with applicable standards and working practises.

    [Schneider Electric]

    Распределительные щиты, включая главный распределительный щит низкого напряжения (ГРЩ), играют решающую роль в обеспечении надежности электроустановки. Они должны отвечать требованиям соответствующих стандартов, определяющих конструкцию и порядок изготовления НКУ распределения электроэнергии.

    В распределительном щите выполняется прием электроэнергии и ее распределение по отдельным цепям, каждая из которых контролируется и защищается плавкими предохранителями или автоматическими выключателями.
    Распределительный щит состоит из функциональных блоков, включающих в себя все электрические и механические элементы, необходимые для выполнения требуемой функции. Распределительный щит представляет собой ключевое звено в цепи обеспечения надежности.

    Тип распределительного щита должен соответствовать области применения. Конструкция и изготовление распределительного щита должны удовлетворять требованиям применимых стандартов и учитывать накопленную практику применения.

    [Перевод Интент]

     

    5654

    Рис. Schneider Electric

    With Prisma Plus G you can be sure to build 100% Schneider Electric switchboards that are safe, optimised:

    > All components (switchgear, distribution blocks, prefabricated connections, etc.) are perfectly rated and coordinated to work together;

    > All switchboard configurations, even the most demanding ones, have been tested.

    You can prove that your switchboard meets the current standards, at any time.

    You can be sure to build a reliable electrical installation and give your customers full satisfaction in terms of dependability and safety for people and the installation.

    Prisma Plus G with its discreet design, blends harmoniously into all tertiary and industrial buildings, including in entrance halls and passageways.

    With Prisma Plus G you can build just the right switchboard for your customer, sized precisely to fit costs and needs.

    With this complete, prefabricated and tested system, it's easy to upgrade your installation and still maintain the performance levels.

    > The wall-mounted and floor-standing enclosures combine easily with switchboards already in service.

    > Devices can be replaced or added at any time.

    [Schneider Electric]

    С помощью оболочек Prisma Plus G можно создавать безопасные распределительные щиты, на 100 % состоящие из изделий Schneider Electric:

    > все изделия (коммутационная аппаратура, распределительные блоки, готовые заводские соединения и т. д.) полностью совместимы механически и электрически;

    > все варианты компоновки распределительных щитов, в том числе для наиболее ответственных применений, прошли испытания.

    В любое время вы можете доказать, что ваши распределительные щиты полностью соответствуют требованиям действующих стандартов.

    Вы можете быть полностью уверены в том, что создаете надежные электроустановки, удовлетворяющие всем требованиям безопасности для людей и оборудования

    Благодаря строгому дизайну, распределительные щиты Prisma Plus G гармонично сочетаются с интерьером любого общественного или промышленного здания. Они хорошо смотрятся и в вестибюле, и в коридоре.

    Применяя оболочки Prisma Plus G можно создавать распределительные щиты, точно соответствующие требованиям заказчика как с точки зрения технических характеристик, так и стоимости.

    С помощью данной испытанной системы, содержащей все необходимые компоненты заводского изготовления можно легко модернизировать существующую электроустановку и поддерживать её уровни производительности.

    > Навесные и напольные оболочки можно легко присоединить к уже эксплуатируемым распределительным щитам.

    > Аппаратуру можно заменять или добавлять в любое время.

    [Перевод Интент]

     

    The switchboard, central to the electrical installation.

    Both the point of arrival of energy and a device for distribution to the site applications, the LV switchboard is the intelligence of the system, central to the electrical installation.

    [Schneider Electric]

    Распределительный щит – «сердце» электроустановки.

    Низковольтное комплектное устройство распределения является «сердцем» электроустановки, поскольку именно оно принимает электроэнергию из сети и распределяет её по территориально распределенным нагрузкам.

    [Перевод Интент]

    Тематики

    EN

    DE

    FR

    Англо-русский словарь нормативно-технической терминологии > gear

  • 47 switchgear

    1. распределительное устройство
    2. коммутационное устройство
    3. коммутационная аппаратура
    4. аппаратура распределения

     

    аппаратура распределения
    Общий термин для коммутационных аппаратов и их комбинаций с относящимися к ним устройствами управления, измерения, защиты и регулирования, а также для узлов, в которых такие аппараты и устройства соединяются с соответствующими фидерами, комплектующим оборудованием, оболочками и опорными конструкциями, предназначенных, в принципе, для использования в системах производства, передачи, распределения и преобразования электрической энергии.
    МЭК 60050(441-11-02).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]

    EN

    switchgear
    a general term covering switching devices and their combination with associated control, measuring, protective and regulating equipment, also assemblies of such devices and equipment with associated interconnections, accessories, enclosures and supporting structures, intended in principle for use in connection with generation, transmission, distribution and conversion of electric energy
    [IEV number 441-11-02]

    FR

    appareillage de connexion
    terme général applicable aux appareils de connexion et à leur combinaison avec des appareils de commande, de mesure, de protection et de réglage qui leur sont associés, ainsi qu'aux ensembles de tels appareils avec les connexions, les accessoires, les enveloppes et les supports correspondants, destinés en principe à être utilisés dans le domaine de la production, du transport, de la distribution et de la transformation de l'énergie électrique
    [IEV number 441-11-02]

     

    Тематики

    • аппарат, изделие, устройство...

    EN

    DE

    • Schaltanlagen und/oder Schaltgeräte für Energieverteilung

    FR

     

    коммутационная аппаратура
    коммутационное оборудование


    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

     

    коммутационное устройство
    Устройство, предназначенное для обеспечения или прерывания подачи электрического тока в электрические цепи.
    Примечание - Коммутационное устройство может выполнять одну или обе эти функции.
    [ГОСТ ЕН 1070-2003]

    коммутационное устройство
    -
    [IEV number 442-01-46]

    EN

    switching device
    a device designed to make or break the current in one or more electric circuits
    Source: 441-14-01 MOD
    [IEV number 442-01-46]

    switchgear

    any of several devices used for opening and closing electric circuits, esp those that pass high currents
    [Collins]

    FR

    dispositif de coupure
    appareil destiné à établir ou à interrompre le courant dans un ou plusieurs circuits électriques
    Source: 441-14-01 MOD
    [IEV number 442-01-46]

    Параллельные тексты EN-RU

    distribution board

    assembly containing different types of switchgear and controlgear associated with one or more outgoing electric circuits fed from one or more incoming electric circuits, together with terminals for the neutral and protective conductors.

    [IEV number 826-16-08]

    распределительная панель

    НКУ, состоящее из коммутационных устройств или устройств защиты (например, плавких предохранителей), присоединенных к одной или нескольким выходным цепям с питанием от одной или нескольких входящих цепей, а также зажимов для нейтрального проводника и проводников цепей защиты. Оно может также содержать сигнальные устройства и другие устройства контроля.

    [ ГОСТ Р 51321. 3-99 ( МЭК 60439-3-90)]


    Тематики

    • аппарат, изделие, устройство...

    EN

    DE

    FR

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    Англо-русский словарь нормативно-технической терминологии > switchgear

  • 48 DS

    1. цифровой стабилизатор
    2. Релаксация
    3. расширение спектра по методу прямой последовательности
    4. распределенное тестирование на одном уровне
    5. разъединитель
    6. прямая последовательность
    7. проектный стандарт
    8. пораженная секунда
    9. пароохладитель
    10. набор данных
    11. дуплексное разнесение
    12. динамическое рассеивание
    13. динамическое переключение
    14. двухсторонняя дискета
    15. водосточная труба
    16. вниз по потоку
    17. барабанный переключатель

     

    барабанный переключатель

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    вниз по потоку

    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    Тематики

    EN

     

    водосточная труба

    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    Тематики

    EN

     

    двухсторонняя дискета

    [Е.С.Алексеев, А.А.Мячев. Англо-русский толковый словарь по системотехнике ЭВМ. Москва 1993]

    Тематики

    EN

     

    динамическое переключение
    динамическая коммутация


    [Е.С.Алексеев, А.А.Мячев. Англо-русский толковый словарь по системотехнике ЭВМ. Москва 1993]

    Тематики

    Синонимы

    EN

     

    динамическое рассеивание

    [Е.С.Алексеев, А.А.Мячев. Англо-русский толковый словарь по системотехнике ЭВМ. Москва 1993]

    Тематики

    EN

     

    дуплексное разнесение
    (Радио)частотный разнос между соответствующими радиостволами прямого и обратного направлений (МСЭ-R F.746-7).
    [ http://www.iks-media.ru/glossary/index.html?glossid=2400324]

    Тематики

    • электросвязь, основные понятия

    EN

     

    набор данных
    Идентифицированная совокупность физических записей, организованная одним из установленных в системе обработки данных способов и представляющая файлы или части файлов в среде хранения.
    [ ГОСТ 20886-85]

    набор данных
    Множество элементов данных, объединенных в отдельное целое для решения определенной задачи.
    Чаще всего набор данных представляется в виде файла, сообщения либо блока данных.
    [Гипертекстовый энциклопедический словарь по информатике Э. Якубайтиса]
    [ http://www.morepc.ru/dict/]

    набор данных
    НД
    -
    [ ГОСТ Р МЭК 61850-7-2-2009]

      НАБОР ДАННЫХ (НД)

    НД представляет собой набор ссылок на данные внутри информационной модели устройства. В НД могут быть включены как отдельные атрибуты данных (например, запись PTOC1.Str.general будет соответствовать одному логическому сигналу пуска защиты), так и логические узлы целиком (например PTOC1). Устройства могут поддерживать различное количество наборов данных. Кроме того, устройства могут иметь фиксированные (то есть когда набор данных нельзя изменить) либо конфигурируемые наборы данных. Также возможны различные степени свободы конфигурации наборов данных: изменение данных, изменение наименования и т.п. Использование наборов данных проиллюстрировано на рис. 3. При рассмотрении контроллера присоединения, на который заведены сигналы о положении всех разъединителей и заземлителей рассматриваемого присоединения, в устройстве должны присутствовать логические узлы, соответствующие каждому из аппаратов (в нашем случае – XSWI1...5). Примером набора данных может служить DATASET с наименованием SwitchPositions, включающий в себя элементы данных Pos каждого из указанных логических узлов. В дальнейшем составленный набор данных может использоваться, например, для сохранения событий в журнале при каждом изменении положения коммутационного аппарата (с использованием сервиса Log), отправки отчета о событии (с использованием сервиса Report) либо быстрого сообщения о событии (с использованием сервиса GOOSE).   Рис. 3. Использование наборов данных  

    При описании информационной модели устройства в нотации МЭК 61850-6 для размещения описаний наборов данных используется системный логический узел LLN0. Наличие логического узла LLN0 является обязательным для каждого логического устройства. При этом не в каждом логическом устройстве могут размещаться наборы данных, поэтому при проектировании и наладке коммуникаций по МЭК 61850 требуется внимательно проверять размещение наборов данных в логических устройствах. Информацию о том, в каком логическом устройстве должны размещаться наборы данных,обычно предоставляет производитель в сопроводительной документации. Подробнее информация об этом будет рассмотрена в будущих публикациях, затрагивающих язык конфигурирования SCL, описанный шестой главой стандарта.

    [ http://www.news.elteh.ru/arh/2012/77/04.php]

    Тематики

    EN

     

    пароохладитель

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    пораженная секунда
    (МСЭ-T G.705).
    [ http://www.iks-media.ru/glossary/index.html?glossid=2400324]

    Тематики

    • электросвязь, основные понятия

    EN

     

    проектный стандарт
    Проектный стандарт еще не определен окончательно, но уже опубликован. Проектные стандарты CiA неизменны в течение одного года.
    [ http://can-cia.com/fileadmin/cia/pdfs/CANdictionary-v2_ru.pdf]

    Тематики

    EN

     

    прямая последовательность
    Метод расширения спектра при передаче сигнала, основанный на умножении информационной последовательности на опорный псевдослучайный сигнал с заведомо известными свойствами. При приеме полезная информация выделяется из сигнала известной структуры с помощью алгоритмов свертки.
    [Л.М.Невдяев. Мобильная связь 3-го поколения. Москва, 2000 г.]

    Тематики

    EN

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

     

    распределенное тестирование на одном уровне
    Абстрактный метод тестирования, при котором верхний тестер располагается в тестируемой системе, а точка наблюдения и контроля (PCO) находится на верхней границе сервиса (IUT) для тестирования на одном из уровней протокола. Тестовые события описываются в терминах абстрактных примитивов сервиса (ASP) на верхнем уровне над IUT и ASP и/или PDU для нижнего тестера PCO. 
    [ http://www.lexikon.ru/dict/net/index.html]

    Тематики

    EN

     

    расширение спектра по методу прямой последовательности
    Метод формирования широкополосного сигнала, при котором исходный двоичный сигнал преобразуется в псевдослучайную последовательность для манипуляции несущей. В эфир передается шумоподобный сигнал, обладающий всеми свойствами аддитивного белого шума. Расширение спектра сигнала в n раз с использованием DSSS позволяет уменьшить спектральную плотность мощности сигнала во столько же раз (МСЭ-R SM.1055).
    [ http://www.iks-media.ru/glossary/index.html?glossid=2400324]

    Тематики

    • электросвязь, основные понятия

    EN

     

    цифровой стабилизатор

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

    Англо-русский словарь нормативно-технической терминологии > DS

  • 49 distribution

    1. распределительное устройство
    2. распределительная сеть
    3. распределение характеристики
    4. распределение (в биотехнологии)
    5. внедрение (в практику)

     

    внедрение
    1. Процесс планомерного перевода объекта (предприятия или организации, системы управления, отдельного процесса или его элемента) из существующего состояния в новое, предусмотренное проектом.
    2. Распространение нововведений, достижение практического использования прогрессивных идей, изобретений, результатов научных исследований.
    [ http://www.lexikon.ru/dict/buh/index.html]

    Тематики

    EN

     

    распределительная сеть
    Часть энергетической системы, которая предназначена для распределения электроэнергии и работает, как правило, на напряжении до 110 кВ.
    [ ГОСТ Р 54325-2011 (IEC/TS 61850-2:2003)]

    Тематики

    EN

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    3.1.2.1 распределение характеристики (distribution): Распределение вероятностей наблюдаемой характеристики, описывающее ее вероятностное поведение.

    Примечание 1 - Распределение вероятностей наблюдаемой характеристики может быть представлено, например, в виде ранжированных результатов наблюдений или гистограммы, построенной по результатам наблюдений. Распределение вероятностей позволяет описать все свойства наблюдаемой характеристики за исключением последовательности, в которой получены данные.

    Примечание 2 - Распределение характеристики зависит от преобладающих условий получения данных. Таким образом, для получения достоверной информации о распределении характеристики необходимо установить условия получения данных.

    Примечание 3 - Важно знать вид распределения (нормальное, лог-нормальное и т.п.) до прогнозирования или оценки показателя воспроизводимости процесса, показателей его функционирования (пригодности), индексов или доли несоответствующих единиц продукции.

    [3534-2:2006, пункт 2.5.1]

    Источник: ГОСТ Р ИСО 21747-2010: Статистические методы. Статистики пригодности и воспроизводимости процесса для количественных характеристик качества оригинал документа

    Англо-русский словарь нормативно-технической терминологии > distribution

  • 50 disconnect switch

    1. разъединитель
    2. размыкающий переключатель
    3. выключатель-разъединитель

     

    выключатель-разъединитель
    Выключатель в разомкнутом положении, удовлетворяющий требованиям к разъединителю.
    МЭК 60050(441-14-12).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]

    EN

    switch-disconnector
    a switch which, in the open position, satisfies the isolating requirements specified for a disconnector
    [IEV number 441-14-12]

    FR

    interrupteur-sectionneur
    interrupteur qui, dans sa position d'ouverture, satisfait aux conditions d'isolement spécifiées pour un sectionneur
    [IEV number 441-14-12]

    004

    Тематики

    • аппарат, изделие, устройство...

    EN

    DE

    FR

     

    размыкающий переключатель

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Англо-русский словарь нормативно-технической терминологии > disconnect switch

  • 51 isolating switch

    1. разъединитель
    2. выключатель-разъединитель

     

    выключатель-разъединитель
    Выключатель в разомкнутом положении, удовлетворяющий требованиям к разъединителю.
    МЭК 60050(441-14-12).
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]

    EN

    switch-disconnector
    a switch which, in the open position, satisfies the isolating requirements specified for a disconnector
    [IEV number 441-14-12]

    FR

    interrupteur-sectionneur
    interrupteur qui, dans sa position d'ouverture, satisfait aux conditions d'isolement spécifiées pour un sectionneur
    [IEV number 441-14-12]

    004

    Тематики

    • аппарат, изделие, устройство...

    EN

    DE

    FR

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Англо-русский словарь нормативно-технической терминологии > isolating switch

  • 52 disconnect

    1. разъединить
    2. разъединитель
    3. отключение абонента
    4. отключать от сети
    5. выключать

     

    выключать

    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    Тематики

    EN

     

    отключать от сети
    -
    [Интент]

    Электродвигатель должен быть немедленно (аварийно) отключен от сети в следующих случаях:...
    [Правила эксплуатации электроустановок потребителей]

    Коммутационные аппараты в цепях электродвигателей должны отключать от сети одновременно все проводники, находящиеся под напряжением.
    [ПУЭ]

    Тематики

    EN

     

    отключение абонента
    Процедура интерфейса, выполняющаяся при сбросе исполнителем сигналов управления занятостью линий и шин интерфейса.
    [ ГОСТ Р 50304-92 ]

    Тематики

    • системы для сопряж. радиоэлектр. средств интерфейсные

    Обобщающие термины

    EN

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

     

    разъединить

    [ http://www.iks-media.ru/glossary/index.html?glossid=2400324]

    Тематики

    • электросвязь, основные понятия

    EN

    Англо-русский словарь нормативно-технической терминологии > disconnect

  • 53 isolator

    1. устройство развязки
    2. устройство локализации дефектов
    3. разъединитель
    4. отделитель

     

    отделитель
    -
    [Интент]

    Отделитель служит для отключения обесточенной цепи высокого напряжения за малое время (не более 0,1 с). Он подобен разъединителю, но снабжен быстродействующим приводом.

    [ http://relay-protection.ru/content/view/46/8/1/1/]

    Тематики

    EN

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

     

    устройство локализации дефектов
    устройство локализации неисправностей


    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    Тематики

    Синонимы

    EN

     

    устройство развязки

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

    Англо-русский словарь нормативно-технической терминологии > isolator

  • 54 switchyard

    1. распределительное устройство подстанции
    2. распределительное устройство
    3. открытое распределительное устройство электростанции

     

    открытое распределительное устройство электростанции

    [А.С.Гольдберг. Англо-русский энергетический словарь. 2006 г.]

    Тематики

    EN

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    Англо-русский словарь нормативно-технической терминологии > switchyard

  • 55 switching substation

    1. распределительное устройство
    2. подстанция
    3. переключательный пункт
    4. (электрическое) распределительное устройство

     

    переключательный пункт

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    подстанция
    Электроустановка, предназначенная для преобразования и распределения электрической энергии.
    [ ГОСТ 19431-84]

    подстанция
    Подстанцией (ПС) называется электроустановка, служащая для преобразования и распределения электроэнергии и состоящая из трансформаторов или других преобразователей энергии, распределительных устройств, устройств управления и вспомогательных сооружений.
    [РД 34.20.185-94]

    подстанция

    Электроустановка, предназначенная для приема, преобразования и распределения электрической энергии, состоящая из трансформаторов или других преобразователей электрической энергии, устройств управления, распределительных и вспомогательных устройств по ГОСТ 19431.
    [ ГОСТ 24291-90]

    подстанция электрическая
    Группа установок и оборудования, размещаемая в здании или на открытой площадке, предназначенная для преобразования параметров передаваемой электроэнергии или распределения её
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    электрическая подстанция
    Электроустановка, предназначенная для преобразования и распределения электрической энергии.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    EN

    substation (of a power system)
    a part of an electrical system, con-fined to a given area, mainly including ends of transmission or distribution lines, electrical switchgear and controlgear, buildings and transformers. A substation generally includes safety or control devices (for example protection)
    NOTE – The substation can be qualified according to the designation of the system of which it forms a part. Examples: transmission substation (transmission system), distribution substation, 400 kV or 20 kV substation.
    [IEV number 601-03-02 ]

    FR

    poste (d'un réseau électrique)
    partie d'un réseau électrique, située en un même lieu, comprenant principalement les extrémités des lignes de transport ou de distribution, de l'appareillage électrique, des bâtiments, et, éventuellement, des transformateurs. Un poste comprend généralement les dispositifs destinés à la sécurité et à la conduite du réseau (par exemple les protections)
    NOTE – Selon le type de réseau auquel appartient le poste, il peut être qualifié par la désignation du réseau. Exemples: poste de transport (réseau de transport), poste de distribution, poste à 400 kV, poste à 20 kV.
    [IEV number 601-03-02 ]

    Подстанции с трансформаторами, преобразующие электрическую энергию только по напряжению, называются трансформаторными; а преобразующие электроэнергию по напряжению и другим параметрам (изменение частоты, выпрямление тока), — преобразовательными. На ПС могут устанавливаться два и более, как правило, трехфазных трансформатора. Установка более двух трансформаторов принимается на основе технико-экономических расчетов, а также в случаях, когда на ПС применяется два средних напряжения. При отсутствии трехфазного трансформатора необходимой мощности, а также при транспортных ограничениях возможно применение группы однофазных трансформаторов. Подстанция, как правило, состоит из нескольких РУ разных ступеней напряжения, соединенных между собой трансформаторной (автотрансформаторной) связью;
    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]

    Тематики

    Синонимы

    EN

    DE

    FR

     

    распределительное устройство
    Распределительным устройством (РУ) называется электроустановка, служащая для приема и распределения электроэнергии и содержащая сборные и соединительные шины, коммутационные аппараты, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [РД 34.20.185-94]

    распределительное устройство

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.
    Примечание. К устройствам управления относятся аппараты и связывающие их элементы обеспечивающие контроль, измерение, сигнализацию и выполнение команд.
    [ ГОСТ 24291-90]
    [ ГОСТ Р 53685-2009]

    электрическое распределительное устройство
    распределительное устройство
    Устройство, предназначенное для приема и распределения электроэнергии на одном напряжении и содержащее коммутационные аппараты и соединяющие их сборные соединительные устройства.
    Примечание. В состав распределительного устройства дополнительно могут входить устройства защиты и управления
    [ОСТ 45.55-99]

    распределительное устройство
    Электроустановка, служащая для приема и распределения электроэнергии и содержащая коммутационные аппараты, сборные и соединительные шины, вспомогательные устройства (компрессорные, аккумуляторные и др.), а также устройства защиты, автоматики и измерительные приборы.
    [ПОТ Р М-016-2001]
    [РД 153-34.0-03.150-00]

    устройство распределительное
    Совокупность аппаратов и приборов для приёма и распределения электроэнергии одного напряжения, вырабатываемой электростанцией или преобразуемой подстанцией
    [Терминологический словарь по строительству на 12 языках (ВНИИИС Госстроя СССР)]

    EN

    switching substation
    a substation which includes switchgear and usually busbars, but no power transformers
    [IEV number 605-01-02]

    FR

    poste de sectionnement
    poste de coupure

    poste comprenant des organes de manoeuvre et généralement des jeux de barres, à l'exclusion de transformateurs de puissance
    [IEV number 605-01-02]

    В качестве РУ 6—10 кВ используется сборка высокого напряжения с однополюсными разъединителями и вертикальным расположением фаз одного присоединения и одна камера КСО с выключателем нагрузки и предохранителями для подключения трансформатора. Для РУ 0,4 кВ применяются сборки низкого напряжения с предохранителями и вертикальным расположением фаз одного присоединения.
    На ПС применяются открытые (ОРУ), закрытые (ЗРУ) или комплектные (КРУ) распределительные устройства.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]


    КЛАССИФИКАЦИЯ

    В общем случае ПС и РУ являются составной частью электроустановок, которые различаются:

    • по назначению:
      • генерирующие,
      • преобразовательно-распределительные,
      • потребительские.

        Генерирующие электроустановки служат для выработки электроэнергии, преобразовательно-распределительные электроустановки преобразуют электроэнергию в удобный для передачи и потребления вид, передают ее и распределяют между потребителями;

     Шкала номинальных напряжений ограничена сравнительно небольшим числом стандартных значений, благодаря чему изготавливается небольшое число типоразмеров машин и оборудования, а электросети выполняются более экономичными. В установках трехфазного тока номинальным напряжением принято считать напряжение между фазами (междуфазовое напряжение). Согласно ГОСТ 29322—92 установлена следующая шкала номинальных напряжений:

    для электросетей переменного тока частотой 50 Гц междуфазовое напряжение должно быть: 12, 24, 36, 42, 127, 220, 380 В; 3, 6, 10, 20, 35, 110, 150, 220, 330, 500, 750 и 1150 кВ;
    для электросетей постоянного тока: 12, 24, 36, 48, 60, 110, 220, 440, 660, 825, 3000 В и выше.

    Тупиковые ПС получают питание по одной или двум тупиковым ВЛ.

    Ответвительные ПС присоединяются ответвлением к одной или двум проходящим ВЛ с односторонним или двухсторонним питанием.

    Проходные ПС включаются в рассечку одной или двух проходящих ВЛ с односторонним или двухсторонним питанием.

    Узловые ПС кроме питающих имеют отходящие радиальные или транзитные ВЛ.

    • по способу управления ПС могут быть:
      • только с телесигнализацией,
      • телеуправляемыми с телесигнализацией,
      • с телесигнализацией и управлением с общеподстанционного пункта управления (ОПУ).


    Подстанции оперативно обслуживаются постоянным дежурным персоналом на щите управления, дежурными на дому или оперативно-выездными бригадами (ОВБ). Ремонт ПС осуществляется специализированными выездными бригадами централизованного ремонта или местным персоналом подстанции.

    В РУ напряжением до 1000 В провода, шины, аппараты, приборы и конструкции выбирают как по нормальным условиям работы (напряжению и току), так и по термическим и динамическим воздействиям токов коротких замыканий (КЗ) или предельно допустимой отключаемой мощности.

    В РУ и ПС напряжением выше 1000 В расстояния между электрооборудованием, аппаратами, токоведущими частями, изоляторами, ограждениями и конструкциями устанавливаются так, чтобы при нормальном режиме работы электроустановки возникающие физические явления (температура нагрева, электрическая дуга, выброс газов, искрение и др.) не могли привести к повреждению оборудования и КЗ.

    [ http://energy-ua.com/elektricheskie-p/klassifikatsiya.html]
     



    Several different classifications of switchgear can be made:

    A single line-up may incorporate several different types of devices, for example, air-insulated bus, vacuum circuit breakers, and manually operated switches may all exist in the same row of cubicles.

    Ratings, design, specifications and details of switchgear are set by a multitude of standards. In North America mostly IEEE and ANSI standards are used, much of the rest of the world uses IEC standards, sometimes with local national derivatives or variations.

    [Robert W. Smeaton (ed) Switchgear and Control Handbook 3rd Ed., Mc Graw Hill, new York 1997]
    [ http://en.wikipedia.org/wiki/High_voltage_switchgear]

    Тематики

    Синонимы

    EN

    DE

    FR

    3 (электрическое) распределительное устройство; РУ

    Электроустановка, предназначенная для приема и распределения электрической энергии на одном напряжении и содержащая коммутационные аппараты и соединяющие их сборные шины [секции шин], устройства управления и защиты.

    Примечание. К устройствам управления относятся аппараты и связывающие их элементы, обеспечивающие контроль, измерение, сигнализацию и выполнение команд

    605-01-02**

    de Schaltstation

    en switching substation

    fr poste de sectionnement, poste de coupure

    Источник: ГОСТ 24291-90: Электрическая часть электростанции и электрической сети. Термины и определения оригинал документа

    Англо-русский словарь нормативно-технической терминологии > switching substation

  • 56 disconnecting switch

    1. разъединитель
    2. размыкающий переключатель

     

    размыкающий переключатель

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Англо-русский словарь нормативно-технической терминологии > disconnecting switch

  • 57 disconnect device

    1. разъединитель

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Англо-русский словарь нормативно-технической терминологии > disconnect device

  • 58 disconnecting device

    1. устройство отключения
    2. разъединитель

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

     

    устройство отключения

    [Я.Н.Лугинский, М.С.Фези-Жилинская, Ю.С.Кабиров. Англо-русский словарь по электротехнике и электроэнергетике, Москва, 1999 г.]

    Тематики

    • электротехника, основные понятия

    EN

    Англо-русский словарь нормативно-технической терминологии > disconnecting device

  • 59 disconnector

    1. разъединитель

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    3.1.46 разъединитель (disconnector): Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, соответствующий нормированным требованиям.

    Источник: ГОСТ Р 54828-2011: Комплектные распределительные устройства в металлической оболочке с элегазовой изоляцией (КРУЭ) на номинальные напряжения 110 кВ и выше. Общие технические условия оригинал документа

    Англо-русский словарь нормативно-технической терминологии > disconnector

  • 60 isolating facility

    1. разъединитель

     

    разъединитель
    Контактный коммутационный аппарат, в разомкнутом положении отвечающий требованиям к функции разъединения.
    Примечание.
    1 Это определение отличается от формулировки МЭК 60050(441-14-05), поскольку требования к функции разъединения не ограничиваются соблюдением изолирующего промежутка.
    [ ГОСТ Р 50030. 1-2000 ( МЭК 60947-1-99)]
    2 Разъединитель способен включать и отключать цепь с незначительным током или при незначительном изменении напряжения на зажимах каждого из полюсов разъединителя.
    Разъединитель может проводить токи в нормальных условиях работы, а также в течение определенного времени в аномальных условиях работы выдерживать токи короткого замыкания.

    0043 Условное обозначение контакта разъединителя

    [ ГОСТ Р 50030. 3-99 ( МЭК 60947-3-99)]

    разъединитель
    Контактный коммутационный аппарат, который обеспечивает в отключенном положении изоляционный промежуток, удовлетворяющий нормированным требованиям.
    Примечания
    1 Разъединитель способен размыкать и замыкать цепь при малом токе или малом изменении напряжения на выводах каждого из его полюсов. Он также способен проводить токи при нормальных условиях в цепи и проводить в течение нормированного времени токи при ненормальных условиях, таких как короткое замыкание.
    2 Малые токи - это такие токи, как емкостные токи вводов, шин, соединений, очень коротких кабелей, токи постоянно соединенных ступенчатых сопротивлений выключателей и токи трансформаторов напряжения и делителей. Для номинальных напряжений до 330 кВ включительно ток, не превышающий 0,5 А, считается малым током по этому определению; для номинального напряжения от 500 кВ и выше и токов, превышающих 0,5 А, необходимо проконсультироваться с изготовителем, если нет особых указаний в руководствах по эксплуатации разъединителей.
    3 К малым изменениям напряжения относятся изменения напряжения, возникающие при шунтировании регуляторов индуктивного напряжения или выключателей.
    4 Для разъединителей номинальным напряжением от 110 кВ и выше может быть установлена коммутация уравнительных токов.
    [ ГОСТ Р 52726-2007]

    EN

    disconnector
    a mechanical switching device which provides, in the open position, an isolating distance in accordance with specified requirements
    NOTE – A disconnector is capable of opening and closing a circuit when either negligible current is broken or made, or when no significant change in the voltage across the terminals of each of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit.
    [IEV number 441-14-05]

    disconnector

    IEV 441-14-05 is applicable with the following additional notes:
    NOTE 1
    "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections, very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents of voltage transformers and dividers. For rated voltages of 420 kV and below, a current not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and currents exceeding 0,5 A, the manufacturer should be consulted.
    "No significant change in voltage" refers to such applications as the by-passing of induction voltage regulators or circuit-breakers.
    NOTE 2
    For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current switching may be assigned
    [IEC 62271-102]

    FR

    sectionneur
    appareil mécanique de connexion qui assure, en position d'ouverture, une distance de sectionnement satisfaisant à des conditions spécifiées
    NOTE – Un sectionneur est capable d'ouvrir et de fermer un circuit lorsqu'un courant d'intensité négligeable est interrompu ou établi, ou bien lorsqu'il ne se produit aucun changement notable de la tension aux bornes de chacun des pôles du sectionneur. Il est aussi capable de supporter des courants dans les conditions normales du circuit et de supporter des courants pendant une durée spécifiée dans des conditions anormales telles que celles du court-circuit.
    [IEV number 441-14-05]

    Указанные в 5.3.2 перечислениях а)-d) устройства отключения ( выключатель-разъединитель, разъединитель или выключатель) должны:

    • изолировать электрооборудование от цепей питания и иметь только одно положение ОТКЛЮЧЕНО (изоляция) и одно положение ВКЛЮЧЕНО, четко обозначаемые символами «О» и «I» [МЭК 60417-5008 (DB:2002-10) и МЭК 60417-5007 (DB:2002-10), см. 10.2.2];
    • иметь видимое разъединение или индикатор положения, который может указывать положение ОТКЛЮЧЕНО только в случае, если все контакты в действительности открыты, т.е. разомкнуты и удалены друг от друга на расстояние, удовлетворяющее требованиям по изолированию;
    • быть снабжены расположенным снаружи ручным приводом (например, ручкой). Исключение для управляемых внешним источником энергии, когда воздействие вручную невозможно при наличии иного внешнего привода. Если внешние приводы не используются для выполнения аварийных функций управления, то рекомендуется применять ЧЕРНЫЙ и СЕРЫЙ цвета для окраски ручного привода (см. 10.7.4 и 10.8.4);
    • обладать средствами для запирания в положении ОТКЛЮЧЕНО (например, с помощью висячих замков). При таком запирании возможность как дистанционного, так и местного включения должна быть исключена;

    [ ГОСТ Р МЭК 60204-1-2007]


    Разъединители служат для создания видимого разрыва, отделяющего выводимое в ремонт оборудование от токоведущих частей, находящихся под напряжением, для безопасного производства работ.
    Разъединители не имеют дугогасящих устройств и поэтому предназначаются для включения и отключения электрических цепей при отсутствии тока нагрузки и находящихся только под напряжением или даже без напряжения. Лишь в некоторых случаях допускается включение и отключение разъединителями небольших токов, значительно меньше номинальных.
    Разъединители используются также при различного рода переключениях в схемах электрических соединений подстанций, например при переводе присоединений с одной системы шин на другую.
    Требования, предъявляемые к разъединителям с точки зрения оперативного обслуживания, следующие:

    1. Разъединители в отключенном положении должны создавать ясно видимый разрыв цепи, соответствующий классу напряжения установки.
    2. Приводы разъединителей должны иметь устройства фиксации в каждом из двух оперативных положений: включенном и отключенном. Кроме того, они должны иметь надежные упоры, ограничивающие поворот главных ножей на угол больше заданного.
    3. Опорные изоляторы и изолирующие тяги должны выдерживать механическую нагрузки при операциях.
    4. Главные ножи разъединителей должны иметь блокировку с ножами стационарных заземлителей и не допускать возможности одновременного включения тех и других.
    5. Разъединители должны беспрепятственно включаться и отключаться при любых наихудших условиях окружающей среды (например, при обледенении).
    6. Разъединители должны иметь надлежащую изоляцию, обеспечивающую не только надежную работу при возможных перенапряжениях и ухудшении атмосферных условий (гроза, дождь, туман), но и безопасное обслуживание.

    [ http://forca.ru/stati/podstancii/obsluzhivanie-razediniteley-otdeliteley-i-korotkozamykateley.html]


    Разъединители применяются для коммутации обесточенных при помощи выключателей участков токоведущих систем, для переключения РУ с одной ветви на другую, а также для отделения на время ревизии или ремонта силового электротехнического оборудования и создания безопасных условий от смежных частей линии, находящихся под напряжением. Разъединители способны размыкать электрическую цепь только при отсутствии в ней тока или при весьма малом токе. В отличие от выключателей разъединители в отключенном состоянии образуют видимый разрыв цепи. После отключения разъединителей с обеих сторон объекта, например выключателя или трансформатора, они должны заземляться с обеих сторон либо при помощи переносных заземлителей, либо специальных заземляющих ножей, встраиваемых в конструкцию разъединителя.
    [ http://relay-protection.ru/content/view/46/8/1/1/]


    Параллельные тексты EN-RU

    b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector;
    [IEC 60204-1-2006]

    б) разъединитель с или без предохранителей, соответствующий требованиям МЭК 60947-3 со вспомогательным контактом, срабатывающим до того, как разомкнутся главные контакты разъединителя, используемым для коммутации другого аппарата, отключающего питание цепей нагрузки.
    [Перевод Интент]

    Тематики

    • высоковольтный аппарат, оборудование...
    • релейная защита
    • электротехника, основные понятия

    Классификация

    >>>

    EN

    DE

    FR

    Смотри также

    Англо-русский словарь нормативно-технической терминологии > isolating facility

См. также в других словарях:

  • Circuit Gilles Villeneuve — The Hairpin (L Epingle) on Circuit Gilles Villeneuve Location Montreal, Quebec, Canada Time zone GMT −5 …   Wikipedia

  • Circuit integrity — fireproofing of cable trays in Lingen/Ems, Germany using calcium silicate board system qualified to DIN 4102 …   Wikipedia

  • Circuit of the Americas — Location Travis County, near Austin, Texas Time zone UTC 6 (standard) / 5 (DST) Coordinates …   Wikipedia

  • Circuit Showdown — Category Auto Racing Series Country or region Philippines Inaugural season 2010 Official website …   Wikipedia

  • Circuit Park Zandvoort — Zandvoort today Location Burgemeester van Alphenstraat 108, 2041 KP Zandvoort, Netherlands Time zone CET (UTC+01) Major events …   Wikipedia

  • Circuit (film) — Circuit DVD cover Directed by Dirk Shafer Produced by Gregory Hinton Michael J. Roth Steven J. Wolfe …   Wikipedia

  • Circuit de Nevers Magny-Cours — Location Magny Cours, France Time zone GMT +1 (DST: +2) Major events …   Wikipedia

  • Circuit total limitation — (CTL) is one of the present day standards for electrical panels sold in the United States according to the National Electrical Code. The 1965 edition of the NEC, article 384 15 was the first reference to the circuit total limitation of… …   Wikipedia

  • Circuit quantum electrodynamics — (circuit QED) provide the means to study the fundamental interaction between light and matter. As in the field of cavity quantum electrodynamics a single photon within a single mode cavity coherently couples to a quantum object (atom). In… …   Wikipedia

  • circuit board — ➔ board1 * * * circuit board UK US noun [C] IT ► a set of electrical connections made by thin lines of metal fixed onto a surface, used in computers and other electronic equipment: »The motherboard is the main circuit board in a computer. → See… …   Financial and business terms

  • Circuit de Calafat — Location L Ametlla de Mar, Catalonia, Spain Time zone GMT +1 Length 3.250 km (2.019 mi) …   Wikipedia

Поделиться ссылкой на выделенное

Прямая ссылка: