    arc-resistant switchgear
    A type of switchgear design which is designed to withstand the effects of an internal arcing fault, without causing harm to personnel who are located in defined areas. It is not intended to withstand these internal arcing fault without possibly causing physical damage to the structure and/or components, but often the physical damage is less with an arc-resistant design.

    There are three classes of protection:
    Type A - eliminates the emission of gases and particles from the front of the switchgear during an internal arcing fault,
    Type B - eliminates the emission of gases and particles from the front and sides of the switchgear during an internal arcing fault,
    Type C - eliminates the emission of gases and particles from the front and sides of the switchgear, from between compartments within the same cell, and between adjacent cells during an internal arcing fault.

    Arc-resistant switchgear has traditionally been metal-clad, but the basic concept could also be applied to other types of switchgear as well.

    arc-proof switchgear
    An incorrect term. Please refer to arc-resistant switchgear
    [Schneider Electric]
    [ http://electrical-engineering-portal.com/glossary-of-medium-voltage-switchgear-terms]

    Параллельные тексты EN-RU

    If the electric arc occurs inside LV switchgear it generates internal overpressures and results in local overheatings which may cause high mechanical and thermal stresses in the equipment.

    Besides, the involved materials can generate hot decomposition products, gases or fumes, which, due to the overpressure, are almost always ejected to the outside of the enclosure thus jeopardizing the operator safety.

    The European Directive 2006/95/EC states the fundamental safety requirements for low voltage electric materials (from 50 V to 1000 V in alternating current, from 75 V to 1500 V in continuos current) to be put on the market within the European Community.

    Among the essential safety requirements defined by this Directive particular importance is given to the need of taking technical measures to prevent “temperature rises, electric arcs or radiations which may result in hazards” from occurring.

    This aspect has always been highly considered for apparatus, but it has been wrongly neglected for electrical switchgear and only in the last 10-15 years it has been catching on both at Italian as well as at international level.

    Safety for the operator and for the installation in case of arcing inside LV switchgear can be obtained through three different design philosophies:
    1. assemblies mechanically capable of withstanding the electric arc (passive protection)
    2. assemblies equipped with devices limiting the effects of internal arcing (active protection)
    3. assemblies equipped with current limiting circuitbreakers.

    These three solutions (also combined together) have found a remakable development in the industrial field and have been successfully applied by the main manufacturers of LV switchgear and controlgear assemblies.

    As it can be seen hereafter by examining the first two solutions, an “active” protection against arc faults is intrinsecally more complex than a “passive” one.

    This because of the presence of additional electromechanical/ electronic devices5 which limit the arcing effects and which, by their nature, may be subject to faults or not-tripping.

    [ABB]

    Дуга, возникшая внутри НКУ, создает внутреннее избыточное давление и вызывает локальный перегрев, что может привести к воздействию на оборудование значительного механического напряжения и перепада температур.

    Кроме того, под воздействием дуги различные материалы разлагаются на продукты, имеющие высокую температуру, в том числе газы и дым, которые почти всегда вырываются из оболочки НКУ под высоким давлением, подвергая опасности оперативный персонал.

    Европейская директива 2006/95/EC определяет основные требования безопасности для низковольтного (от 50 до 1000 В переменного тока и от 75 до 1500 В постоянного тока) оборудования поставляемого на рынок Европейского Сообщества.

    Одно из основных требований безопасности, определяемое данной директивой как наиболее важное, заключается в необходимости предпринять технические меры для предотвращения "подъема температуры, возникновения электрической дуги или излучения", которые могут причинить ущерб.

    Данная проблема всегда учитывалась при создании различных аппаратов, но незаслуженно игнорировалась при разработке электрических комплектных устройств, и только в последние 10-15 лет ей стали уделять должное внимание как в Италии, так и во всем мире.

    При возникновении электрической дуги внутри НКУ безопасность оператора и электроустановки обеспечивается тремя способами:
    1. Конструкция НКУ должна выдерживать механические воздействия, возникающие при горении электрической дуги (пассивная защита).
    2. НКУ должно быть оснащено устройствами, ограничивающими воздействие электрической дуги (активная защита)
    3. НКУ должны быть оснащены токоограничивающими автоматическими выключателями.

    Указанные три способа (применяемые совместно) получили дальнейшее развитие в промышленности и успешно применяются основными изготовителями НКУ распределения и управления.

    Как будет показано далее при рассмотрении первых двух способов, активная защита от дуговых» неисправностей является более сложной, чем пассивная защита.

    Это объясняется необходимостью использования дополнительных электромеханических или электронных устройств, задачей которых является ограничение воздействий дуги и которые сами могут оказаться неисправными и не сработать.

    [Перевод Интент]

    Тематики

    • НКУ (шкафы, пульты,...)

    Синонимы

    EN

    Англо-русский словарь нормативно-технической терминологии > arc-resistant switchgear

  • 42 internal arc-proof switchgear and controlgear assemblу

    1. НКУ с защитой от воздействия электрической дуги

     

    НКУ с защитой от воздействия электрической дуги
    комплектное устройство с защитой от электрической дуги
    низковольтное комплектное устройство с защитой от электрической дуги
    НКУ распределения и управления с защитой от электрической дуги
    -
    [Интент]

    EN

    arc-resistant switchgear
    A type of switchgear design which is designed to withstand the effects of an internal arcing fault, without causing harm to personnel who are located in defined areas. It is not intended to withstand these internal arcing fault without possibly causing physical damage to the structure and/or components, but often the physical damage is less with an arc-resistant design.

    There are three classes of protection:
    Type A - eliminates the emission of gases and particles from the front of the switchgear during an internal arcing fault,
    Type B - eliminates the emission of gases and particles from the front and sides of the switchgear during an internal arcing fault,
    Type C - eliminates the emission of gases and particles from the front and sides of the switchgear, from between compartments within the same cell, and between adjacent cells during an internal arcing fault.

    Arc-resistant switchgear has traditionally been metal-clad, but the basic concept could also be applied to other types of switchgear as well.

    arc-proof switchgear
    An incorrect term. Please refer to arc-resistant switchgear
    [Schneider Electric]
    [ http://electrical-engineering-portal.com/glossary-of-medium-voltage-switchgear-terms]

    Параллельные тексты EN-RU

    If the electric arc occurs inside LV switchgear it generates internal overpressures and results in local overheatings which may cause high mechanical and thermal stresses in the equipment.

    Besides, the involved materials can generate hot decomposition products, gases or fumes, which, due to the overpressure, are almost always ejected to the outside of the enclosure thus jeopardizing the operator safety.

    The European Directive 2006/95/EC states the fundamental safety requirements for low voltage electric materials (from 50 V to 1000 V in alternating current, from 75 V to 1500 V in continuos current) to be put on the market within the European Community.

    Among the essential safety requirements defined by this Directive particular importance is given to the need of taking technical measures to prevent “temperature rises, electric arcs or radiations which may result in hazards” from occurring.

    This aspect has always been highly considered for apparatus, but it has been wrongly neglected for electrical switchgear and only in the last 10-15 years it has been catching on both at Italian as well as at international level.

    Safety for the operator and for the installation in case of arcing inside LV switchgear can be obtained through three different design philosophies:
    1. assemblies mechanically capable of withstanding the electric arc (passive protection)
    2. assemblies equipped with devices limiting the effects of internal arcing (active protection)
    3. assemblies equipped with current limiting circuitbreakers.

    These three solutions (also combined together) have found a remakable development in the industrial field and have been successfully applied by the main manufacturers of LV switchgear and controlgear assemblies.

    As it can be seen hereafter by examining the first two solutions, an “active” protection against arc faults is intrinsecally more complex than a “passive” one.

    This because of the presence of additional electromechanical/ electronic devices5 which limit the arcing effects and which, by their nature, may be subject to faults or not-tripping.

    [ABB]

    Дуга, возникшая внутри НКУ, создает внутреннее избыточное давление и вызывает локальный перегрев, что может привести к воздействию на оборудование значительного механического напряжения и перепада температур.

    Кроме того, под воздействием дуги различные материалы разлагаются на продукты, имеющие высокую температуру, в том числе газы и дым, которые почти всегда вырываются из оболочки НКУ под высоким давлением, подвергая опасности оперативный персонал.

    Европейская директива 2006/95/EC определяет основные требования безопасности для низковольтного (от 50 до 1000 В переменного тока и от 75 до 1500 В постоянного тока) оборудования поставляемого на рынок Европейского Сообщества.

    Одно из основных требований безопасности, определяемое данной директивой как наиболее важное, заключается в необходимости предпринять технические меры для предотвращения "подъема температуры, возникновения электрической дуги или излучения", которые могут причинить ущерб.

    Данная проблема всегда учитывалась при создании различных аппаратов, но незаслуженно игнорировалась при разработке электрических комплектных устройств, и только в последние 10-15 лет ей стали уделять должное внимание как в Италии, так и во всем мире.

    При возникновении электрической дуги внутри НКУ безопасность оператора и электроустановки обеспечивается тремя способами:
    1. Конструкция НКУ должна выдерживать механические воздействия, возникающие при горении электрической дуги (пассивная защита).
    2. НКУ должно быть оснащено устройствами, ограничивающими воздействие электрической дуги (активная защита)
    3. НКУ должны быть оснащены токоограничивающими автоматическими выключателями.

    Указанные три способа (применяемые совместно) получили дальнейшее развитие в промышленности и успешно применяются основными изготовителями НКУ распределения и управления.

    Как будет показано далее при рассмотрении первых двух способов, активная защита от дуговых» неисправностей является более сложной, чем пассивная защита.

    Это объясняется необходимостью использования дополнительных электромеханических или электронных устройств, задачей которых является ограничение воздействий дуги и которые сами могут оказаться неисправными и не сработать.

    [Перевод Интент]

    Тематики

    • НКУ (шкафы, пульты,...)

    Синонимы

    EN

    Англо-русский словарь нормативно-технической терминологии > internal arc-proof switchgear and controlgear assemblу

См. также в других словарях:

  • High-temperature superconductivity — Unsolved problems in physics What causes superconductivity at temperatures above 50 kelvin? High temperature superconductors (abbreviated high Tc or HTS) are materials that have a superconducting transition temperature (Tc) above 30 K… …   Wikipedia

  • high-pressure phenomena — ▪ physics Introduction       changes in physical, chemical, and structural characteristics that matter undergoes when subjected to high pressure. pressure thus serves as a versatile tool in materials research, and it is especially important in… …   Universalium

  • Temperature — This article is about the thermodynamic property. For other uses, see Temperature (disambiguation). A map of global long term monthly average surface air temperatures i …   Wikipedia

  • high — /haɪ / (say huy) adjective 1. having a great or considerable reach or extent upwards; lofty; tall. 2. having a specified extent upwards. 3. situated above the ground or some base; elevated. 4. far above the horizon, as a heavenly body. 5. lying… …  

  • High-performance liquid chromatography — An HPLC. From left to right: A pumping device generating a gradient of two different solvents, a steel enforced column and an apparatus for measuring the absorbance. Acronym HPLC Classification Chromatography …   Wikipedia

  • Structure formation — refers to a fundamental problem in physical cosmology. The universe, as is now known from observations of the cosmic microwave background radiation, began in a hot, dense, nearly uniform state approximately 13.7 Gyr ago. [cite journal |author=D.… …   Wikipedia

  • Temperature gradient gel electrophoresis — (TGGE) and Denaturing Gradient Gel Electrophoresis (DGGE) are forms of electrophoresis which use either a temperature or chemical gradient to denature the sample as it moves across an acrylamide gel. TGGE and DGGE can be applied to nucleic acids… …   Wikipedia

  • Lamellar structure — Lamellar structures or microstructures are composed of fine, alternating layers of different materials in the form of lamellae. They are often observed in cases where a phase transformation front moves quickly, leaving behind two solid products,… …   Wikipedia

  • Structure d'impact de Chassenon — Astroblème de Rochechouart Chassenon Astroblème de Rochechouart Chassenon Image de synthèse du cratère quelques années après l’impact. Localisation Astre …   Wikipédia en Français

  • Structure d'impact de Rochechouart — Astroblème de Rochechouart Chassenon Astroblème de Rochechouart Chassenon Image de synthèse du cratère quelques années après l’impact. Localisation Astre …   Wikipédia en Français

  • Structure d'impact de Rochechouart-Chassenon — Astroblème de Rochechouart Chassenon Astroblème de Rochechouart Chassenon Image de synthèse du cratère quelques années après l’impact. Localisation Astre …   Wikipédia en Français

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»