2 параллельная система ИБП
параллельная система ИБП
-
[Интент]Parallel Operation: The system shall have the option to install up to four (4) UPSs in parallel configuration for redundancy or capacity.
1. The parallel UPS system shall be of the same design, voltage, and frequency. UPS modules of different size ratings shall be permitted to be paralleled together for purposes of increased capacity or UPS module redundancy. The UPSs in the parallel configuration shall not be required to have the same load capacity rating.
2. Parallel Capacity: With N+0 system-level redundancy, up to 2MW of load can be supported by the system.
3. Parallel Redundancy: With N+1 system-level redundancy, up to 1.5MW of load can be supported by the system, and only the UPS being replaced must be isolated from the source (bypass operation is not required for the entire system during the UPS replacement procedure).
4. Output control: A load sharing circuit shall be incorporated into the parallel control circuits to ensure that under no-load conditions, no circulating current exists between modules. This feature also allows each UPS to share equal amounts of the total critical load bus. The output voltage, output frequency, output phase angle, and output impedance of each module shall operate in uniformity to ensure correct load sharing. This control function shall not require any additional footprint and shall be an integral function of each UPS. The static bypass switches shall be connected in parallel.
5. Parallel System Controls: To avoid single points of failure, the UPS system shall have no single dedicated control system designed to control the operation of the parallel UPS system. Control of and direction of parallel UPSs shall take place via a master/slave relationship, where the first UPS to receive logic power asserts itself as a master. In the event of a master failure, a slave UPS shall take the role of master and assume the responsibility of the previous master UPS. Regardless of which UPS is master or slave, user changes to the system status, such as request for bypass, can be done from any UPS connected to the bus and all UPS on the bus shall transfer in simultaneously.
6. Communication: Communication between modules shall be connected so that the removal of any single cable shall not jeopardize the integrity of the parallel communication system. Load sharing communications shall be galvanically isolated for purposes of fault tolerance between UPS modules. A UPS module's influence over load sharing shall be inhibited in any mode where the UPS inverter is not supporting its output bus. Transfers to and from bypass can be initiated from any online UPS in the system.
7. Display: Each UPS multi-color LCD touch screen user interface shall be capable of using an active touch screen mimic bus to show the quantity of UPS(s) connected to the critical bus, as well as the general status of each UPS, such as circuit breaker status information. Any touchscreen display shall support the configuration of the [entire parallel] system and shall provide event and alarm data for all UPSs in the parallel configuration. A Virtual Display Application shall be available for download to the customer’s computer and shalll support remote monitoring of a complete system with up to 4 UPSs in parallel.
8. Battery runtime: Each UPS must have its own battery solution. The battery solution for the entire system can be a combination of standard and third-party batteries, but each UPS must use only one battery solution – either standard or third-party batteries.
9. Switchgear: A custom switchgear option shall be required for parallel operation.
[Schneider Electric]Тематики
EN
Русско-английский словарь нормативно-технической терминологии > параллельная система ИБП
См. также в других словарях:
History of the graphical user interface — The graphical user interface, understood as the use of graphic icons and a pointing device to control a computer, has over the last four decades a steady history of incremental refinements built on some constant core principles. Several vendors… … Wikipedia
Custom built PC — A custom built (or assembled) PC is a computer case that is built from components (parts of the system unit) at hand under the individual person or organization from scratch. The main advantage of manual assembly is the ability to pick up a… … Wikipedia
Custom-fit — is a broad term which could be defined as tailor made. To this respect, mass customization could be defined as a massive personalization or personalization for everybody. In the development of the term, a customized product would imply the… … Wikipedia
Custom-Fit — Customization is a broad term which could be defined as tailor made. To this respect, mass customization could be defined as a massive personalization or personalization for everybody.In the development of the term, a customized product would… … Wikipedia
Command-line interface — Screenshot of a sample Bash session. GNOME Terminal 3, Fedora 15 … Wikipedia
Musical Instrument Digital Interface — MIDI (Musical Instrument Digital Interface, IPAEng|ˈmɪdi) is an industry standard protocol that enables electronic musical instruments, computers, and other equipment to communicate, control, and synchronize with each other. MIDI allows computers … Wikipedia
Speech Application Programming Interface — The Speech Application Programming Interface or SAPI is an API developed by Microsoft to allow the use of speech recognition and speech synthesis within Windows applications. To date a number of versions of the API have been released, which have… … Wikipedia
Scalable Link Interface — For other uses, see SLI (disambiguation). Scalable Link Interface Manufacturer NVIDIA Predecessor Scan Line Interleave … Wikipedia
Ultrasound Research Interface — An Ultrasound Research Interface (URI) is a software tool loaded onto a diagnostic clinical ultrasound device which provides functionality beyond typical clinical modes of operation. Before an ultrasound image can be displayed to the user, it… … Wikipedia
Google Custom Search — (formerly known as Google Co op) is a platform provided by Google that allows web developers to feature specialized information in web searches, refine and categorize queries and create customized search engines, based on Google Web Search.… … Wikipedia
IEEE 1394 interface — Infobox Computer Hardware Bus name = IEEE 1394 interface invent date = 1995 invent name = Apple super name = super date = width = 1 numdev = 63 speed = 400–3200 Mbit/s style = s hotplug = Yes external = YesThe IEEE 1394 interface is a serial bus… … Wikipedia