    Dictionary of Engineering, architecture and construction > continuous rating

  • 2 длительный допустимый ток

    1. courant permanent admissible, m
    2. courant admissible, m

     

    (длительный) допустимый ток
    Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме
    [ ГОСТ Р МЭК 60050-826-2009]

    Этот ток обозначают IZ
    [ ГОСТ Р 50571. 1-2009 ( МЭК 60364-1: 2005)]

    EN

    (continuous) current-carrying capacity
    ampacity (US)
    maximum value of electric current which can be carried continuously by a conductor, a device or an apparatus, under specified conditions without its steady-state temperature exceeding a specified value
    [IEV number 826-11-13]

    ampacity
    The current in amperes that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
    [National Electrical Cod]

    FR

    courant (permanent) admissible, m
    valeur maximale du courant électrique qui peut parcourir en permanence, un conducteur, un dispositif ou un appareil, sans que sa température de régime permanent, dans des conditions données, soit supérieure à la valeur spécifiée
    [IEV number 826-11-13]

    Ampacity, the term is defined as the maximum amount of current a cable can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

    • its insulation temperature rating;
    • conductor electrical properties for current;
    • frequency, in the case of alternating currents;
    • ability to dissipate heat, which depends on cable geometry and its surroundings;
    • ambient temperature.

    Electric wires have some resistance, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

    The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

    In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run governs the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the de-rating factor is tabulated in a nation's wiring regulations.

    Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75 and 90 degrees Celsius, often with an ambient air temperature of 30°C. In the U.S., 105°C is allowed with ambient of 40°C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200 or 250°C.

    The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material.

    For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

    Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

    When designing an electrical system, one will normally need to know the current rating for the following:

    Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

    [http://en.wikipedia.org/wiki/Ampacity]

    Тематики

    • электротехника, основные понятия

    Синонимы

    EN

    DE

    • Dauerstrombelastbarkeit, f
    • Strombelastbarkeit, f

    FR

    • courant admissible, m
    • courant permanent admissible, m

    Русско-французский словарь нормативно-технической терминологии > длительный допустимый ток

См. также в других словарях:

  • Maximum continuous rating — (MCR) is defined as the maximum output (MW) that a generating station[clarification needed] is capable of producing continuously under normal conditions over a year. Under ideal conditions, the actual output could be higher than the MCR.[1]… …   Wikipedia

  • Rating system of the Royal Navy — The rating system of the British Royal Navy was used by the British Royal Navy between the middle of the 17th century and the middle of the 19th century to categorise sailing warships according to the number and weight of their guns.Origins… …   Wikipedia

  • Continuous distillation — Image 1: Typical industrial distillation towers Image 2: A crude oil vacuum distillation column as used in oil refineries …   Wikipedia

  • engine rating — The engine power permitted for specific flight conditions and timings (e.g., takeoff power, continuous rating, maximum afterburner rating, emergency rating) …   Aviation dictionary

  • maximum cruise rating — The maximum continuous power to be obtained in the autolean mixture setting …   Aviation dictionary

  • Audio power — Sound measurements Sound pressure p, SPL Particle velocity v, SVL Particle displacement ξ Sound intensity I, SIL Sound power Pac Sound power level SWL Sound energy Sound energy density …   Wikipedia

  • Diesel generator — A Cummins diesel generator of 500kVA in a tourist resort in Egypt …   Wikipedia

  • British Rail Class 25 — Infobox Locomotive name = British Rail Class 25 powertype = Diesel electric caption = Class 25 locomotive stands on Springs Branch Traction Maintenance Depot at Wigan roadnumber = D5151–D5299, D7500–D7677; later 25001–25327 totalproduction = 327… …   Wikipedia

  • Relay — This article is about the electrical component. For other uses, see Relay (disambiguation). Automotive style miniature relay, dust cover is taken off A relay is an electrically operated switch. Many relays use an electromagnet to operate a… …   Wikipedia

  • Gas engine — This article is about engines that use gaseous fuel. For gasoline engines, see Petrol engine. For other uses, see Internal combustion engine. Model of an S type Hartop Gas Engine. A gas engine means an engine running on a gas, such as coal gas,… …   Wikipedia

  • Power supply unit (computer) — Power supply unit with top cover removed A power supply unit (PSU) supplies direct current (DC) power to the other components in a computer. It converts general purpose alternating current (AC) electric power from the mains (110 V to… …   Wikipedia

Поделиться ссылкой на выделенное

Прямая ссылка:
Нажмите правой клавишей мыши и выберите «Копировать ссылку»